9440500990 Rev D

327

DECS-250N

Analog Expansion Module

Note

1.

If the AEM-2020 is providing one end of the J1939 bus, a 120

Ω,

½ watt terminating resistor should be installed across terminals
P1- LO (CANL) and P1- HI (CANH).

2.

If the AEM-2020 is not part of the J1939 bus, the stub connecting
the AEM-2020 to the bus should not exceed 914 mm (3 ft) in
length.

3.

The maximum bus length, not including stubs, is 40 m (131 ft).

4.

The J1939 drain (shield) should be grounded at one point only. If
grounded elsewhere, do not connect the drain to the AEM-2020.

Figure 174. CAN Bus Interface with AEM-2020 providing One End of the Bus

Figure 175. CAN Bus Interface with DECS-250N providing One End of the Bus