beautypg.com

Basler Electric DECS-250N User Manual

Page 247

background image

9440500990 Rev D

231

DECS-250N

Modbus™ Communication

Group

Name

Register

Type

Sz

R/W

Unit

Range

27P

Secondary Mode

43184

Uint32

4

R W

n/a

Disabled=0 Enabled=1

27P

Secondary Pickup

43186

Float

4

R W

V

Disabled=0, 1 - 600000

27P

Secondary Time Delay

43188

Float

4

R W

ms

100 - 60000

59P

Primary Mode

43190

Uint32

4

R W

n/a

Disabled=0 Enabled=1

59P

Primary Pickup

43192

Float

4

R W

V

Disabled=0, 0 - 600000

59P

Primary Time Delay

43194

Float

4

R W

ms

100 - 60000

59P

Secondary Mode

43196

Uint32

4

R W

n/a

Disabled=0 Enabled=1

59P

Secondary Pickup

43198

Float

4

R W

V

Disabled=0, 0 - 600000

59P

Secondary Time Delay

43200

Float

4

R W

ms

100 - 60000

81O

Primary Mode

43202

Uint32

4

R W

n/a

Disabled=0 Over=1

81O

Primary Pickup

43204

Float

4

R W

Hz

Disabled=0, 30 - 70

81O

Primary Time Delay

43206

Float

4

R W

ms

100 - 300000

81O

Secondary Mode

43208

Uint32

4

R W

n/a

Disabled=0 Over=1

81O

Secondary Pickup

43210

Float

4

R W

Hz

Disabled=0, 30 - 70

81O

Secondary Time Delay

43212

Float

4

R W

ms

100 - 300000

81U

Primary Mode

43214

Uint32

4

R W

n/a

Disabled=0 Under=2

81U

Primary Pickup

43216

Float

4

R W

Hz

Disabled=0, 30 - 70

81U

Primary Time Delay

43218

Float

4

R W

ms

100 - 300000

81U

Primary Voltage Inhibit

43220

Float

4

R W

%

Disabled=0, 50 - 100

81U

Secondary Mode

43222

Uint32

4

R W

n/a

Disabled=0 Under=2

81U

Secondary Pickup

43224

Float

4

R W

Hz

Disabled=0, 30 - 70

81U

Secondary Time Delay

43226

Float

4

R W

ms

100 - 300000

81U

Secondary Voltage Inhibit

43228

Float

4

R W

%

Disabled=0, 50 - 100

40Q

Primary Mode

43230

Uint32

4

R W

n/a

Disabled=0 Enabled=1

40Q

Primary Pickup

43232

Float

4

R W

%

Disabled=0, 0 - 150

40Q

Primary Time Delay

43234

Float

4

R W

ms

Instantaneous=0, 0 - 300000

40Q

Secondary Mode

43236

Uint32

4

R W

n/a

Disabled=0 Enabled=1

40Q

Secondary Pickup

43238

Float

4

R W

%

Disabled=0, 0 - 150

40Q

Secondary Time Delay

43240

Float

4

R W

ms

Instantaneous=0, 0 - 300000

32R

Primary Mode

43242

Uint32

4

R W

n/a

Disabled=0 Enabled=4

32R

Primary Pickup

43244

Float

4

R W

%

Disabled=0, 0 - 150

32R

Primary Time Delay

43246

Float

4

R W

ms

Instantaneous =0, 0 - 300000

32R

Secondary Mode

43248

Uint32

4

R W

n/a

Disabled=0 Enabled=4

32R

Secondary Pickup

43250

Float

4

R W

%

Disabled=0, 0 - 150

32R

Secondary Time Delay

43252

Float

4

R W

ms

Instantaneous=0, 0 - 300000

Field Overcurrent

Timing Mode, Protection Primary

43254

Uint32

4

R W

n/a

Definite Timing=0
Inverse Timing=1

Field Overcurrent

Time Dial, Protection Primary

43256

Float

4

R W

n/a

0.1 – 20

Field Overcurrent

Timing Mode, Protection
Secondary

43258

Uint32

4

R W

n/a

Definite Timing=0
Inverse Timing=1

Field Overcurrent

Time Dial, Protection Secondary

43260

Float

4

R W

n/a

0.1 – 20

24

Primary Mode

43262

Uint32

4

R W

n/a

Disabled=0,Enabled=1

24

Primary Definite Time Pickup 1

43264

Float

4

R W

n/a

0.5 – 6

24

Primary Definite Time Pickup 2

43266

Float

4

R W

n/a

0.5 – 6

24

Primary Definite Time Delay 1

43268

Float

4

R W

ms

50 – 600000

24

Primary Definite Time Delay 2

43270

Float

4

R W

ms

50 – 600000

24

Primary Inverse Time Pickup

43272

Float

4

R W

n/a

0.5 – 6

24

Primary Time Dial Trip

43274

Float

4

R W

n/a

0 – 9.9

24

Primary Time Dial Reset

43276

Float

4

R W

n/a

0 – 9.9

24

Primary Curve Exponent

43278

Uint32

4

R W

n/a

0.5=0,1=1,2=2

24

Secondary Mode

43280

Uint32

4

R W

n/a

Disabled=0,Enabled=1

This manual is related to the following products: