Basler Electric DECS-250N User Manual
Page 303
![background image](https://www.manualsdir.com/files/773924/content/doc303.png)
9440500990 Rev D
287
DECS-250N
PROFIBUS Communication
Instance Name
Inst. #
Type
RW
Key Name
Unit
Range
Remote Analog In 3
208
Float
R/W
Threshold 3
Activation Delay GG
Sec
0 - 300
Remote Analog In 3
208
Float
R/W
Threshold 4 Pickup GG
No
Unit
-9999 - 9999
Remote Analog In 3
208
Float
R/W
Threshold 4
Activation Delay GG
Sec
0 - 300
Remote Analog In 3
208
Float
R/W
Param Min GG
No
Unit
-9999 - 9999
Remote Analog In 3
208
Float
R/W
Param Max GG
No
Unit
-9999 - 9999
Remote Analog In 3
208
Float
R/W
Current Min GG
mA
4 - 20
Remote Analog In 3
208
Float
R/W
Current Max GG
mA
4 - 20
Remote Analog In 3
208
Float
R/W
Voltage Min GG
V
0 - 10
Remote Analog In 3
208
Float
R/W
Voltage Max GG
V
0 - 10
Remote Analog In 4
209
UINT32 R/W
Stop Mode Inhibit GG
No
Unit
NO=0 YES=1
Remote Analog In 4
209
UINT32 R/W
Threshold1Type GG
No
Unit
Disabled=0 Over=1 Under=2
Remote Analog In 4
209
UINT32 R/W
Threshold2Type GG
No
Unit
Disabled=0 Over=1 Under=2
Remote Analog In 4
209
UINT32 R/W
Threshold3Type GG
No
Unit
Disabled=0 Over=1 Under=2
Remote Analog In 4
209
UINT32 R/W
Threshold4Type GG
No
Unit
Disabled=0 Over=1 Under=2
Remote Analog In 4
209
UINT32 R/W
Type GG
No
Unit
Voltage=0 Current=1
Remote Analog In 4
210
Float
R/W
Hysteresis GG
%
0 - 100
Remote Analog In 4
210
Float
R/W
Arming Delay GG
Sec
0 - 300
Remote Analog In 4
210
Float
R/W
Threshold 1 Pickup GG
No
Unit
-9999 - 9999
Remote Analog In 4
210
Float
R/W
Threshold 1
Activation Delay GG
Sec
0 - 300
Remote Analog In 4
210
Float
R/W
Threshold 2 Pickup GG
No
Unit
-9999 - 9999
Remote Analog In 4
210
Float
R/W
Threshold 2
Activation Delay GG
Sec
0 - 300
Remote Analog In 4
210
Float
R/W
Threshold 3 Pickup GG
No
Unit
-9999 - 9999
Remote Analog In 4
210
Float
R/W
Threshold 3
Activation Delay GG
Sec
0 - 300
Remote Analog In 4
210
Float
R/W
Threshold 4 Pickup GG
No
Unit
-9999 - 9999
Remote Analog In 4
210
Float
R/W
Threshold 4
Activation Delay GG
Sec
0 - 300
Remote Analog In 4
210
Float
R/W
Param Min GG
No
Unit
-9999 - 9999
Remote Analog In 4
210
Float
R/W
Param Max GG
No
Unit
-9999 - 9999
Remote Analog In 4
210
Float
R/W
Current Min GG
mA
4 - 20