Generator Condition

A dead generator is recognized by the DECS-250N when the generator voltage decreases below the
dead generator threshold

A

for the duration of the dead generator activation delay

B

.

A failed generator is recognized when the generator voltage or frequency does not meet the established
generator stability criteria for the duration of the failed generator activation delay

C

. Generator stability

parameters are described in Generator Stability.

Generator Stability

Before initiating a breaker closure (tying the generator to a stable or dead bus), the generator voltage
must be stable. Several settings are used to determine generator stability. These settings include pickup
and dropout levels for overvoltage

D

, undervoltage

E

, overfrequency

F

, and under-frequency

G

. Recognition of

generator stability is further controlled by a generator stability activation delay

H

. Breaker closure is not

considered if the voltage conditions are not within the stability pickup and dropout settings for the duration
of the stability activation delay.

Bus Condition

A dead bus is recognized by the DECS-250N when the bus voltage decreases below the dead bus
threshold

I

for the duration of the dead bus activation delay

J

.

A failed bus is recognized when the bus voltage or frequency does not meet the established stability
criteria for the duration of the failed bus activation delay

K

. Bus stability parameters are described in Bus

Stability.

Bus Stability

Before initiating a breaker closure (tying the generator to a live bus), the bus voltage must be stable.
Several settings are used to determine bus stability. These settings include pickup and dropout levels for
overvoltage

L

, undervoltage

M

, overfrequency

N

, and underfrequency

O

. Recognition of bus stability is further

controlled by a bus stability activation delay

P

. Breaker closure is not considered if the voltage conditions

are not within the stability pickup and dropout settings for the duration of the stability activation delay.