Basler Electric DECS-250N User Manual

Page 250

background image

234

9440500990 Rev D

Modbus™ Communication

DECS-250N

Name

Register

Type

Byte

s

R/W

Unit

Range

RMS Generator Volts Phase A to B

47251

Float

4

R

n/a

n/a

RMS Generator Volts Phase B to C

47253

Float

4

R

n/a

n/a

RMS Generator Volts Phase C to A

47255

Float

4

R

n/a

n/a

Average RMS L-L Volts

47257

Float

4

R

n/a

n/a

Generator Current IB in amps

47259

Float

4

R

n/a

n/a

Generator Apparent Power in kVA

47261

Float

4

R

n/a

n/a

Generator Real Power in kW

47263

Float

4

R

n/a

n/a

Generator Reactive Power in kvar

47265

Float

4

R

n/a

n/a

Power Factor

47267

Float

4

R

n/a

n/a

Generator Frequency in Hertz

47269

Float

4

R

n/a

n/a

Bus Frequency in Hertz

47271

Float

4

R

n/a

n/a

RMS Bus Voltage in Volts

47273

Float

4

R

n/a

n/a

Field Voltage in Volts

47275

Float

4

R

n/a

n/a

Field Current in Amps

47277

Float

4

R

n/a

n/a

Var/PF Controller Output in Volts

47279

Float

4

R

Per Unit

n/a

Phase Angle Between Phase B Voltage and
Current

47281

Float

4

R

n/a

n/a

Auxiliary Input in Volts

47283

Float

4

R

n/a

n/a

Current Input for Load Compensation

47285

Float

4

R

n/a

n/a

Null Balance in Percent

47287

Float

4

R

n/a

n/a

Error Signal to Autotracking Loop

47289

Float

4

R

n/a

n/a

Active Controller Output

47291

Float

4

R

n/a

n/a

PF State

47293

Uint16

2

R

n/a

n/a

Generator State

47294

Uint16

2

R

n/a

n/a

Status of Front Panel LEDs

47295

Uint16

2

R

n/a

(bit flags, 0 = off, 1 = on for all
LEDs except Null Balance and
Internal Tracking, which are
reversed): b0 = Null Balance, b1
= Tracking, b2 = Pre-position, b3
= Upper Limit, b4 = Lower Limit,
b5 = Edit, b6-b15 = unassigned

Voltage Matching Status

47296

Uint16

2

R

n/a

n/a

Protection Status Bit Flags 1

47297

Uint16

2

R

n/a

(0 = clear, 1 = condition present):
b0 = field overvoltage, b1 = field
overcurrent, b2 = gen.
Undervoltage, b3 = gen.
overvoltage, b4 =
underfrequency, b5 = in OEL, b6
= in UEL, b7 = in FCR mode, b8
= loss of sensing voltage, b9 =
setpoint at lower limit, b10 =
setpoint at upper limit, b11 = gen.
failed to build up, b12 = gen.
below 10Hz, b13 = unassigned,
b14 = exciter diode open, b15 =
exciter diode shorted.

Reserved

47298

Float

4

R

n/a

n/a

Active Operating Setpoint in Percent

47300

Float

4

R

n/a

n/a

Contact Input States

47302

Uint16

2

R

n/a

n/a