beautypg.com

Contact outputs, Watchdog output, Programmable outputs – Basler Electric DECS-250N User Manual

Page 54

background image

38

9440500990 Rev D

Contact Inputs and Outputs

DECS-250N

Figure 23. Contact Input Label Text

A

Label Text: Enter a string of up to 64 alphanumeric characters.

See the Terminals and Connectors chapter for an illustration of the programmable input terminals.

Contact Outputs

BESTCOMSPlus Navigation Path: Settings Explorer, Programmable Outputs, Contact Outputs

HMI Navigation Path: Not available through HMI.

DECS-250N contact outputs consist of a dedicated watchdog output and 11 programmable outputs. An
additional 18 contact outputs are available with the optional Contact Expansion Module (CEM-2020H).
The optional CEM-2020 provides an additional 24 contact outputs. Contact Basler Electric for ordering
information.

Watchdog Output

This SPDT (Form C) output changes state during the following conditions:

Control power is lost

Normal firmware execution ceases

Transfer Watchdog Trip is asserted in BESTlogicPlus.

Watchdog output connections are made at terminals WTCHD1 (normally open), WTCHD (common), and
WTCHD2 (normally closed).

Programmable Outputs

The 11 programmable, normally-open contact outputs can be configured to annunciate DECS-250N
status, active alarms, active protection functions, and active limiter functions. Using BESTlogicPlus
programmable logic, these outputs can be used as part of a user-configured logic scheme to control and
annunciate a variety of system conditions and contingencies. Information about using the programmable
outputs in a logic scheme is provided in the BESTlogicPlus chapter.

To make the programmable contact outputs easier to identify, you can assign a custom name

A

that relates

to the functions of your system. Figure 24 shows the BESTCOMSPlus Contact Outputs screen where
each of the 11 outputs can be assigned a custom name.

This manual is related to the following products: