Operating power input, Modes of operation, Firing pulse mode – Basler Electric DECS-250N User Manual
Page 189: Single-phase selection, Bridge operating power configuration

9440500990 Rev D
173
DECS-250N
Configuration
Figure 150. Sensing Transformer Ratings and Configuration
A
Generator PT Primary Voltage: Adjustable from 1 to 500,000 Vac in 1 Vac increments.
B
Generator PT Secondary Voltage: Adjustable from 1 to 600 Vac in 1 Vac increments.
C
Generator PT Phase Rotation: Select ABC or ACB rotation.
D
Generator Voltage Connections: Select CA or 3W-D.
E
Generator CT Primary Current: Adjustable from 1 to 99,999 Aac in 1 Aac increments.
F
Generator CT Secondary Current: Select 1 or 5 Aac.
G
Generator CT Configuration: Select B or CT_ABC.
H
Bus PT Primary Voltage: Adjustable from 1 to 500,000 Vac in 1 Vac increments.
I
Bus PT Secondary Voltage: Adjustable from 1 to 600 Vac in 1 Vac increments.
J
Bus Voltage Sensing Connections: Select CA or 3W-D.
Bridge Operating Power Configuration
BESTCOMSPlus Navigation Path: Settings Explorer, System Parameters, Bridge
HMI Navigation Path: Settings, System Parameters, Bridge
DECS-250N bridge operating power configuration includes selection of the input voltage range and mode
of operation. These settings are illustrated in Figure 151.
Operating Power Input
AC voltage range
A
settings for bridge operating power establish the values expected by the DECS-250N.
Modes of Operation
Firing Pulse Mode
Firing Pulse Mode
B
settings for the bridge operating power establish the number of phases expected by
the DECS-250N.
Single-Phase Selection
Single-phase
C
settings establish which pair of phases the DECS-250N expects to supply bridge operating
power. This option is disabled when Three Phase is the selected firing pulse mode.