Offline logic simulator, Bestlogic™plus file management – Basler Electric DECS-250N User Manual
Page 176
![background image](https://www.manualsdir.com/files/773924/content/doc176.png)
160
9440500990 Rev D
BESTlogic
™Plus
DECS-250N
Timing accuracy is
±15 milliseconds.
Figure 132. Pickup and Dropout Timer Logic Blocks
Offline Logic Simulator
You can use the offline logic simulator to test your custom logic before placing it in operation. The state of
various logic elements can be toggled to verify that the logic states travel through the system as
expected.
The offline logic simulator allows you to change the state of various logic elements to illustrate how that
state travels through the system. Before running the logic simulator, you must click the Save button on the
BESTlogicPlus toolbar to save the logic to memory. Changes to the logic (other than changing the state)
are disabled when the simulator is enabled. Colors are selected by clicking the Options button on the
BESTlogicPlus toolbar. By default, Logic 0 is red and Logic 1 is green. Using your mouse, double-click on
a logic element to change its state.
An example of the offline logic simulator is shown in Figure 133. STOP_ENABLE is Logic 0 (red) when
Input 1 is Logic 1 (green), Input 2 is Logic 0 (red), and the inverter is Logic 1 (green).
Figure 133. Offline Logic Simulator Example
BESTlogic™Plus File Management
To manage BESTlogicPlus files, use the Settings Explorer to open the BESTlogicPlus Programmable
Logic tree branch. Use the BESTlogicPlus Programmable Logic toolbar to manage BESTlogicPlus files.
Initiate
Pickup Time
Output
Initiate
Dropout Time
Output
Pickup
Timer
Dropout
Timer
Output
Output
Initiate
Initiate
P0048-03