Basler Electric DECS-250N User Manual
Page 165

9440500990 Rev D
149
DECS-250N
BESTlogic
™Plus
Name
Description
Symbol
Counter
True when the count reaches a user-selected number.
Count Up increments the count when a true is received.
Count Down decrements the count when a true is received.
Reset resets the count to zero when a true is received.
OUTPUT is true when the count reaches the trigger count.
The trigger count is set by the user and is found in Settings Explorer,
BESTlogicPlus Programmable Logic, Logic Counters.
Elements
Table 14 lists the names and descriptions of the elements in the Elements group.
Table 14. Elements Group, Names and Descriptions
Name
Description
Symbol
27
When true, this element blocks, or disables,
the 27 undervoltage protection function.
ALARM RESET
When true, this element resets all active
alarms.
AUTO ENABLE
When true, this element sets the unit in Auto
mode (AVR).
AUTO TRANSFER
ENABLE
When true, this element sets the unit as
secondary. When false, the unit is primary.
CROSS CURRENT
COMPENSATION
DISABLE
When true, this element disables cross current
compensation.
DATALOG
TRIGGER
When true, this element triggers the datalog to
begin recording data.
DROOP DISABLE
When true, this element disables droop when
the unit is operating in AVR mode.
EXTERNAL
TRACKING
DISABLE
When true, this element disables external
tracking.