Basler Electric DECS-250N User Manual
Page 291

9440500990 Rev D
275
DECS-250N
PROFIBUS Communication
Instance Name
Inst. #
Type
RW
Key Name
Unit
Range
Gen Undervolt
164
Float
R/W
Pickup PS
V
1 - 600000
Gen Undervolt
164
Float
R/W
Time Delay PS
ms
100 - 60000
Gen Overvolt
165
UINT32 R/W
Mode PP
No
Unit
DISABLED=0 ENABLED=1
Gen Overvolt
165
UINT32 R/W
Mode PS
No
Unit
DISABLED=0 ENABLED=1
Gen Overvolt
166
Float
R/W
Pickup PP
V
0 - 600000
Gen Overvolt
166
Float
R/W
Time Delay PP
ms
100 - 60000
Gen Overvolt
166
Float
R/W
Pickup PS
V
0 - 600000
Gen Overvolt
166
Float
R/W
Time Delay PS
ms
100 - 60000
Loss of Sensing
167
UINT32 R/W
Mode GG
No
Unit
DISABLED=0 ENABLED=1
Loss of Sensing
167
UINT32 R/W
Sys Option No Sense To
Manual Mode GG
No
Unit
DISABLED=0 ENABLED=1
Loss of Sensing
168
Float
R/W
Time Delay GG
Sec
0 - 30
Loss of Sensing
168
Float
R/W
Voltage Balanced
Level GG
%
0 - 100
Loss of Sensing
168
Float
R/W
Voltage Unbalanced Level
GG
%
0 - 100
81O
169
UINT32 R/W
Mode PP
No
Unit
DISABLED=0 OVER=1
81O
169
UINT32 R/W
Mode PS
No
Unit
DISABLED=0 OVER=1
81O
170
Float
R/W
Pickup PP
Hz
30 - 70
81O
170
Float
R/W
Time Delay PP
ms
100 - 300000
81O
170
Float
R/W
Pickup PS
Hz
30 - 70
81O
170
Float
R/W
Time Delay PS
ms
100 - 300000
81O
170
Float
R/W
Voltage Inhibit PP
%
5 – 100
81O
170
Float
R/W
Voltage Inhibit PS
%
5 – 100
81U
171
UINT32 R/W
Mode PP
No
Unit
DISABLED=0 UNDER=2
81U
171
UINT32 R/W
Mode PS
No
Unit
DISABLED=0 UNDER=2
81U
172
Float
R/W
Pickup PP
Hz
30 - 70
81U
172
Float
R/W
Time Delay PP
ms
100 - 300000
81U
172
Float
R/W
Voltage Inhibit PP
%
5 - 100
81U
172
Float
R/W
Pickup PS
Hz
30 - 70
81U
172
Float
R/W
Time Delay PS
ms
5 - 300000
81U
172
Float
R/W
Voltage Inhibit PS
%
50 - 100
Reverse Power
173
UINT32 R/W
Mode PP
No
Unit
DISABLED=0 ENABLED=4