beautypg.com

Mounting, Mounting considerations, Projection mounting – Basler Electric DECS-250N User Manual

Page 125: Behind-the-panel mounting

background image

9440500990 Rev D

109

DECS-250N

Mounting

Mounting

As delivered, the DECS-250N is configured for projection (wall) mounting. Front panel mounting is
possible with an optional escutcheon kit. Kits are supplied with an escutcheon and screws for securing
the escutcheon to the DECS-250N. For a new installation, request kit part number 9440311101. When
replacing a DECS-200N with the DECS-250N, request kit part number 9440506101. The panel mounting
holes of this kit align with the DECS-200N escutcheon mounting holes so no panel drilling is required.

Mounting Considerations

DECS-250N heat sink orientation necessitates vertical mounting for maximum cooling. Any other
mounting angle will reduce heat dissipation and possibly lead to premature failure of critical components.

The DECS-250N may be mounted anywhere the ambient temperature does not exceed the maximum
operating temperature as listed in the Specifications chapter.

Projection Mounting

Figure 103 illustrates the mounting dimensions for projection (wall) mounting of the DECS-250N.

Behind-the-Panel Mounting

Figure 104 shows the front dimensions of the optional escutcheon mounting plate used with the DECS-
250N for new installations. Panel cutting and drilling dimensions for panel mounting are shown in Figure
105.

Figure 106 shows the front dimensions of the optional escutcheon mounting plate used when replacing a
DECS-200N with the DECS-250N.

This manual is related to the following products: