Basler Electric DECS-250N User Manual
Page 38
![background image](https://www.manualsdir.com/files/773924/content/doc038.png)
22
9440500990 Rev D
Synchronizer
DECS-250N
Figure 13. Generator and Bus Condition Detection Settings
A
Dead Gen Threshold: Adjustable from 0 to 600,000 Vac in 1 Vac increments.
B
Dead Gen Activation Delay: Adjustable from 0.1 to 600 s in 0.1 s increments.
C
Gen Failed Activation Delay: Adjustable from 0.1 to 600 s in 0.1 s increments.
D
Generator Stability Overvoltage Pickup and Dropout: Adjustable from 10 to 600,000 Vac in 1 Vac
increments.
E
Generator Stability Undervoltage Pickup and Dropout: Adjustable from 10 to 600,000 Vac in 1 Vac
increments.
F
Generator Stability Overfrequency Pickup and Dropout: Adjustable from 46 to 64 Hz in 0.05 Hz
increments.
G
Generator Stability Underfrequency Pickup and Dropout: Adjustable from 46 to 64 Hz in 0.05 Hz
increments.
H
Generator Stability Activation Delay: Adjustable from 0.1 to 600 s in 0.1 s increments.