Protection

Figure 27. Overexcitation Protection Settings

A

Definite Time Pickup: Adjustable from 0 or 0.5 to 6.00 in increments of 0.01.

B

Definite Time Delay: Adjustable from 0.05 to 600 seconds in increments of 0.001 seconds.

C

Inverse Time Pickup: Adjustable from 0 or 0.5 to 6.00 in increments of 0.01.

D

Time Dial: Adjustable from 0.0 to 9.9 in increments of 0.1.

E

Reset Dial: Adjustable from 0.0 to 9.9 in increments of 0.1.

F

Mode: Select Enabled or Disabled.

G

Curve Exponent: Select 0.5, 1, or 2

Generator Undervoltage

An undervoltage pickup condition occurs when the sensed generator terminal voltage decreases below
the pickup setting

A

. An undervoltage trip condition occurs if the generator voltage remains below the

pickup threshold for the duration of the time delay setting

B

. Generator undervoltage protection can be

enabled and disabled

C

without altering the pickup and time delay settings. Undervoltage pickup and trip

elements in BESTlogicPlus can be used in a logic scheme to initiate corrective action in response to the
condition. BESTCOMSPlus generator undervoltage settings are illustrated in Figure 28.

Figure 28. Generator Undervoltage Protection Settings

A

Generator Undervoltage Pickup (V): Adjustable from 0 to 600,000 Vac in 1 Vac increments.

B

Generator Undervoltage Time Delay (s): Adjustable from 0.1 to 60 seconds in 0.1 second increments.

C

Generator Undervoltage Enable/Disable: Select Enabled or Disabled.