beautypg.com

Power factor, Pre-position setpoints – Basler Electric DECS-250N User Manual

Page 43

background image

9440500990 Rev D

27

DECS-250N

Regulation

Power Factor

When operating in Power Factor (PF) mode, the DECS-250N controls the var output of the generator to
maintain the Power Factor setpoint

F

as the kW load on the generator varies. The setting range of the PF

setpoint is determined by the PF – Leading

G

and PF – Lagging

H

settings. The length of time required to

adjust the PF setpoint from one limit to the other is controlled by a Traverse Rate setting

I

. A Fine Voltage

Adjustment Band setting

E

defines the upper and lower boundaries of voltage correction when the

DECS-250N is operating in Var or Power Factor regulation modes. PF Active Power Level

J

establishes

the level of generator output power (kW) where the DECS-250N switches to/from Droop
Compensation/Power Factor mode. If the level of power decreases below the setting, the DECS-250N
switches from Power Factor mode to Droop Compensation mode. Conversely, as the level of power
increases above the setting, the DECS-250N switches from Droop Compensation mode to Power Factor
mode. A setting of 0 to 30% may be entered in 0.1% increments.

Power Factor mode settings are illustrated in Figure 16.

Figure 16. Var and Power Factor Regulation Settings

A

Setpoint: Range of adjustment is based on the generator ratings and limited by the Var Minimum (B) and

Var Maximum (C) settings.

B

Min (% of rated): Adjustable from –100 to 100% in 0.1% increments.

C

Max (% of rated): Adjustable from 0 to 100% in 0.1% increments.

D

Traverse Rate (s): Adjustable from 10 to 200 seconds in 1 second increments.

E

Fine Voltage Adjustment Band: Adjustable from 0 to 30% in 0.01% increments.

F

PF Setpoint: Range of adjustment is determined by the PF Leading (G) and Lagging (H) settings.

G

PF – Leading: Adjustable from –1 to –0.5 in 0.005 increments.

H

PF – Lagging: Adjustable from 0.5 to 1 in 0.005 increments.

I

Traverse Rate (s): Adjustable from 10 to 200 seconds in 1 second increments.

J

PF Active Power Level: Adjustable from 0 to 30% in 0.1% increments.

Pre-Position Setpoints

Each regulation mode has three pre-position setpoints which allow the DECS-250N to be configured for
multiple system and application needs. Each pre-position setpoint can be assigned to a programmable
contact input. When the appropriate contact input is closed, the setpoint is driven to the corresponding
pre-position value. Each pre-position function has two settings: Setpoint and Mode. The setting range of
each pre-position setpoint

A

is identical to that of the corresponding control mode setpoint. The Mode

B

setting determines whether or not the DECS-250N will respond to further setpoint change commands
while the pre-position command is being asserted. If the pre-position mode is Release, setpoint change
commands are accepted to raise and lower the setpoint while the pre-position command is being
asserted. Additionally, if the inactive pre-position mode is Release and internal tracking is enabled, the
pre-position value will respond to the tracking function. If the pre-position mode is Maintain, further
setpoint change commands are ignored while the appropriate contact input is closed. Additionally, if the
inactive pre-position mode is Maintain and internal tracking is enabled, the inactive mode will maintain the

This manual is related to the following products: