Basler Electric DECS-250N User Manual
Page 162
146
9440500990 Rev D
BESTlogic
™Plus
DECS-250N
Name
Description
Symbol
Analog
Expansion
Module
Remote RTD
Inputs 1-8
There are four thresholds for each of the eight
Remote RTD Input blocks. Each threshold has a
separate logic block for the pickup and the trip.
Remote RTD Input #1 with its Threshold #1 Pickup
and Trip blocks is shown to the right. For more
details on configuring the Remote RTD Inputs, see
the Analog Expansion Module chapter in this
manual. The pickup block is true when the
threshold is exceeded. The trip block is true when
the corresponding pickup block threshold is
exceeded for the duration of the time delay.
Analog
Expansion
Module
Remote RTD
Inputs, Out of
Range 1-8
Each Remote RTD Input has one Out of Range
Block. True when parameters exceed out of range
threshold. This function alerts the user of an open
or damaged analog input wire.
Analog
Expansion
Module
Remote
Thermocouple
Inputs 1-2
There are four thresholds for both of the Remote
Thermocouple Input blocks. Each threshold has a
separate logic block for the pickup and the trip.
Remote Thermocouple Input #1 with its Threshold
#1 Pickup and Trip blocks is shown to the right. For
more details on configuring the Remote
Thermocouple Inputs, see the Analog Expansion
Module chapter in this manual. The pickup block is
true when the threshold is exceeded. The trip block
is true when the corresponding pickup block
threshold is exceeded for the duration of the time
delay.
Analog
Expansion
Module
Remote
Thermocouple
Inputs, Out of
Range 1-2
Each Remote Thermocouple Input has one Out of
Range Block. True when parameters exceed out of
range threshold. This function alerts the user of an
open or damaged analog input wire.
Output Objects
Physical Outputs
OUT1 - OUT11
Physical Outputs 1 through 11.
Remote Outputs
OUT12 - OUT35
Remote Outputs 12 through 35.
(Available when an optional CEM-2020 is
connected.)
Off-Page Objects
Off-Page Output
Used in conjunction with the Off-Page Input to
transform an output on one logic page into an input
on another logic page. Outputs can be renamed by
right-clicking and selecting Rename Output. Right-
clicking will also show pages that the
corresponding inputs can be found on. Selecting
the page will take you to that page.