Regulation
Figure 19. Paralleled Generators and Line Drop Compensation Settings
A
Droop Compensation Enable: Place a check in the checkbox to enable droop compensation.
B
Reactive Droop Compensation: Adjustable from 0 to +30% in 0.1% increments.
C
Cross-Current Compensation Enable: Place a check in the checkbox to enable cross-current
compensation.
D
Cross-Current Compensation Gain: Adjustable from –30 to +30% in 0.1% increments.
E
Load Share Enable: Place a check in the checkbox to enable load sharing.
F
Load Share Droop: Adjustable from 0 to 30% in 0.1% increments.
G
Load Share Gain: Adjustable from 0 to 1,000 in increments of 0.01.
H
Load Share Washout Filter Time Constant: Adjustable from 0 to 1 in increments of 0.01.
I
Load Share Washout Filter Gain: Adjustable from 0 to 1,000 in increments of 0.01.
J
Load Share ID: Adjustable from 1 to 16 in increments of 1.
K
Line Drop Compensation Enable: Place a check in the checkbox to enable line drop compensation.
L
Line Drop Compensation: Adjustable from 0 to 30% in increments of 0.1%.
Autotracking
BESTCOMSPlus Navigation Path: Settings Explorer, Operating Settings, Autotracking
HMI Navigation Path: Settings, Operating Settings, Autotracking.
Internal regulation mode setpoint tracking and external setpoint tracking are standard features on the
DECS-250N. Autotracking settings are illustrated in Figure 20.
Internal Setpoint Tracking
In applications using a single DECS-250N, internal tracking can be enabled
A
so that the inactive
regulation modes track the active regulation mode.