PROFIBUS Communication

DECS-250N

Instance Name

Inst. #

Type

RW

Key Name

Unit

Range

Bus Metering Per Unit

21

Float

R

bus vavg pu GG

No Unit

-10 - 10

Field Metering

22

Float

R

VX GG

V

-1000 - 1000

Field Metering

22

Float

R

IX GG

Amp

0 - 2000000000

Field Metering

22

Float

R

EDM RIPPLE PERCENT GG

%

n/a

PSS Metering

23

Float

R

V1 GG

V

0 - 2000000000

PSS Metering

23

Float

R

V2 GG

V

0 - 2000000000

PSS Metering

23

Float

R

I1 GG

Amp

0 - 2000000000

PSS Metering

23

Float

R

I2 GG

Amp

0 - 2000000000

PSS Metering

23

Float

R

TERM FREQ DEV GG

No Unit

n/a

PSS Metering

23

Float

R

COMP FREQ DEV GG

No Unit

n/a

PSS Metering

23

Float

R

PSS OUTPUT GG

No Unit

n/a

PSS Metering Per Unit

24

Float

R

pos seq v pu GG

No Unit

-10 - 10

PSS Metering Per Unit

24

Float

R

neq seq v pu GG

No Unit

-10 - 10

PSS Metering Per Unit

24

Float

R

pos seq i pu GG

No Unit

-10 - 10

PSS Metering Per Unit

24

Float

R

neq seq i pu GG

No Unit

-10 - 10

Synchronization

25

Float

R

Slip Angle GG

Deg

-359.9 - 359.9

Synchronization

25

Float

R

Slip Freq GG

Hz

n/a

Synchronization

25

Float

R

Voltage Diff GG

V

n/a

Aux Input Metering

26

Float

R

Value GG (Aux Input Voltage)

V

-9999999 - 9999999

Aux Input Metering

26

Float

R

Value GG (Aux Input Current)

Amp

-9999999 - 9999999

Tracking

27

Float

R

TRACKING ERROR GG

%

n/a

Tracking Status

28

UINT8

R

DECSREGULATORMETER
DECS
INTERNAL TRACKING
ACTIVE

Not active=0, Active=1

Tracking Status

28

UINT8

R

DECSREGULATORMETER
DECS
EXTERNAL TRACKING
ACTIVE

Not active=0, Active=1

Tracking Status

28

UINT8

R

DECSCONTROL DECS
NULL BALANCE

Not active=0, Active=1

Control Panel Setpoint
Metering

29

Float

R

Gen Vol Setpoint GG

V

84 - 144

Control Panel Setpoint
Metering

29

Float

R

Exc Cur Setpoint GG

Amp

0 - 12

Control Panel Setpoint
Metering

29

Float

R

Exc Vol Setpoint GG

V

0 - 75

Control Panel Setpoint
Metering

29

Float

R

Gen Var Setpoint GG

kvar

0 – 41.57

Control Panel Setpoint
Metering

29

Float

R

Gen Pf Setpoint GG

PF

0.5 – -0.5

Control Panel Status

30

UINT8

R

DECSCONTROL DECS
START STOP

Stopped=0, Started=1

Control Panel Status

30

UINT8

R

DECSCONTROL DECS IS IN
AUTOMATIC MODE

Not in automatic=0, In automatic=1

Control Panel Status

30

UINT8

R

DECSCONTROL DECS IS IN
MANUAL MODE

Not in manual=0, In manual=1

Control Panel Status

30

UINT8

R

DECSCONTROL DECS FCR
CONTROLLER ACTIVE

FCR not active=0, FCR active=1

Control Panel Status

30

UINT8

R

DECSCONTROL DECS FVR
CONTROLLER ACTIVE

FVR not active=0, FVR active=1

Control Panel Status

30

UINT8

R

DECSCONTROL DECS VAR
CONTROLLER ACTIVE

VAR not active=0, VAR active=1

Control Panel Status

30

UINT8

R

DECSCONTROL DECS PF
CONTROLLER ACTIVE

PF not active=0, PF active=1

Control Panel Status

30

UINT8

R

DECSCONTROL DECS
PREPOSITION 1 ACTIVE

Active setpoint is not at pre-
position 1 value=0, Active setpoint
is at pre-position 1 value=1