Specifications

Relay Output 10 ......................... RLY 10, RLY 10

Relay Output 11 ......................... RLY 11, RLY 11

Field Power Output

Continuous Rating ............................ 20 Adc
Forcing Rating .................................. 40 Adc for 10 s, 30 Adc for 120 s
Terminals.......................................... F+, F–

Maximum Positive Forcing Voltage

1-Phase
63 Vdc Application ........................... 130 Vdc, 40 Adc
125 Vdc Application ......................... Not recommended
250 Vdc Application ......................... Not recommended

3-Phase
63 Vdc Application ........................... 120 Vdc, 40 Adc
125 Vdc Application ......................... 240 Vdc, 40 Adc
250 Vdc Application ......................... 480 Vdc, 40 Adc

Maximum Negative Forcing Voltage

1-Phase
63 Vdc Application ........................... –105 Vdc, 40 Adc
125 Vdc Application ......................... Not recommended
250 Vdc Application ......................... Not recommended

3-Phase
63 Vdc Application ........................... –100 Vdc, 40 Adc
125 Vdc Application ......................... –200 Vdc, 40 Adc
250 Vdc Application ......................... –400 Vdc, 40 Adc

Minimum Field Resistance

63 Vdc Application ........................... 3.15

125 Vdc Application ......................... 6.25

250 Vdc Application ......................... 12.5

Regulation

FCR Operating Mode

Setpoint Range ................................ 0 to 18 Adc, in increments of 0.1%
Regulation Accuracy ........................ ±1.0% of the nominal value for 10% of the power input voltage

change or 20% of the field resistance change. Otherwise, ±5.0%

FVR Operating Mode

Setpoint Range ................................ 0 to 270 Vdc, in increments of 0.1%
Regulation Accuracy ........................ ±1.0% of the nominal value for 10% of the power input voltage

change or 20% of the field resistance change. Otherwise, ±5.0%

AVR Operating Mode

Setpoint Range ................................ 70 to 120% of rated generator voltage, in increments of 0.1%
Regulation Accuracy ........................ ±0.25% over load range at rated PF with constant generator

frequency and ambient temperature