Basler Electric DECS-250N User Manual
Page 123

9440500990 Rev D
107
DECS-250N
Stability Tuning
Figure 102. Other Mode and Function Gain Settings
A
Var Ki – Integral Gain: Adjustable from 0 to 1,000 in 0.001 increments.
B
Var Kg – Loop Gain: Adjustable from 0 to 1,000 in 0.001 increments.
C
PF Ki – Integral Gain: Adjustable from 0 to 1,000 in 0.001 increments.
D
PF Kg – Loop Gain: Adjustable from 0 to 1,000 in 0.001 increments.
E
OEL Ki – Integral Gain: Adjustable from 0 to 1,000 in 0.001 increments.
F
OEL Kg – Loop Gain: Adjustable from 0 to 1,000 in 0.001 increments.
G
UEL Ki – Integral Gain: Adjustable from 0 to 1,000 in 0.001 increments.
H
UEL Kg – Loop Gain: Adjustable from 0 to 1,000 in 0.001 increments.
I
SCL Ki – Integral Gain: Adjustable from 0 to 1,000 in 0.001 increments.
J
SCL Kg – Loop Gain: Adjustable from 0 to 1,000 in 0.001 increments.
K
VARL Ki – Integral Gain: Adjustable from 0 to 1,000 in 0.1 increments.
L
VARL Kg – Loop Gain: Adjustable from 0 to 1,000 in 0.1 increments.
M
Voltage Matching Ki – Integral Gain: Adjustable from 0 to 1,000 in 0.001 increments.