9440500990 Rev D

247

DECS-250N

PROFIBUS Communication

Instance Name

Inst. #

Type

RW

Key Name

Unit

Range

Synchronizer Metering
Cyclic

5

Float

R

Slip Angle GG

Deg

-359.9 - 359.9

Synchronizer Metering
Cyclic

5

Float

R

Slip Freq GG

Hz

n/a

Synchronizer Metering
Cyclic

5

Float

R

Voltage Diff GG

V

n/a

Limiter Status Cyclic

6

UINT8

R

ALARMS OEL ALM

Not Active=0, Active=1

Limiter Status Cyclic

6

UINT8

R

ALARMS UEL ALM

Not Active=0, Active=1

Limiter Status Cyclic

6

UINT8

R

ALARMS SCL ALM

Not Active=0, Active=1

Limiter Status Cyclic

6

UINT8

R

ALARMS VAR
LIMITER ACTIVE

Not Active=0, Active=1

Limiter Status Cyclic

6

UINT8

R

ALARMS
UNDERFREQUENCYVHZ
ALM

Not Active=0, Active=1

HMI Indicators Cyclic

7

UINT8

R

DECSCONTROL
DECS NULL BALANCE

Not Active=0, Active=1

HMI Indicators Cyclic

7

UINT8

R

DECSPSSMETER
DECS PSS ACTIVE

Not Active=0, Active=1

HMI Indicators Cyclic

7

UINT8

R

DECSREGULATORMETER
DECS
INTERNAL TRACKING
ACTIVE

Not Active=0, Active=1

HMI Indicators Cyclic

7

UINT8

R

DECSCONTROL DECS
PREPOSITION

Active setpoint is not at a pre-
position value=0, Active setpoint is
at a pre-position value=1

HMI Indicators Cyclic

7

UINT8

R

DECSREGULATORMETER
SETPOINT
AT LOWER LIMIT

Active setpoint is not at minimum
value=0, Active setpoint is at
minimum value=1

HMI Indicators Cyclic

7

UINT8

R

DECSREGULATORMETER
SETPOINT
AT UPPER LIMIT

Active setpoint is not at maximum
value=0, Active setpoint is at
maximum value=1

Controller Status Cyclic

8

UINT8

R

DECSCONTROL IN AVR
MODE

Not in AVR mode=0, In AVR
mode=1

Controller Status Cyclic

8

UINT8

R

DECSCONTROL IN FCR
MODE

Not in FCR mode=0, In FCR
mode=1

Controller Status Cyclic

8

UINT8

R

DECSCONTROL IN FVR
MODE

Not in FVR mode=0, In FVR
mode=1

Controller Status Cyclic

8

UINT8

R

DECSCONTROL IN PF
MODE

Not in PF mode=0, In PF mode=1

Controller Status Cyclic

8

UINT8

R

DECSCONTROL IN VAR
MODE

Not in var mode=0, In var mode=1

System Status Cyclic

9

UINT8

R

DECSCONTROL DECS
START STOP

Stopped=0, Started=1

System Status Cyclic

9

UINT8

R

ALARMS IFLIMIT

No field short circuit condition=0,
Field short circuit condition=1

System Status Cyclic

9

UINT8

R

DECSCONTROL DECS
SOFT START ACTIVE

Not in soft start=0, In soft start=1

System Status Cyclic

9

UINT8

R

ALARMREPORT
ALARMOUTPUT

No active alarms=0, Active
alarms=1

System Status Cyclic

9

UINT8

R

DECSCONTROL DECS PF
VAR
ENABLE 52 J K

PF/var not enabled via PLC=0,
PF/var enabled via PLC=1

System Status Cyclic

9

UINT8

R

DECSCONTROL DECS
PARALLEL
ENABLE 52 L M

Parallel not enabled via PLC=0,
Parallel enabled via PLC=1

Local Contact Inputs Cyclic

10

UINT8

R

CONTACTINPUTS
STARTINPUT

Open=0, Closed=1

Local Contact Inputs Cyclic

10

UINT8

R

CONTACTINPUTS
STOPINPUT

Open=0, Closed=1

Local Contact Inputs Cyclic

10

UINT8

R

CONTACTINPUTS INPUT1

Open=0, Closed=1

Local Contact Inputs Cyclic

10

UINT8

R

CONTACTINPUTS INPUT2

Open=0, Closed=1

Local Contact Inputs Cyclic

10

UINT8

R

CONTACTINPUTS INPUT3

Open=0, Closed=1