beautypg.com

Var limiter, Limiter scaling – Basler Electric DECS-250N User Manual

Page 81

background image

9440500990 Rev D

65

DECS-250N

Limiters

Var Limiter

BESTCOMSPlus Navigation Path: Settings Explorer, Operating Settings, Limiters, var

HMI Navigation Path: Settings, Operating Settings, Limiters, VAR

The var limiter can be enabled

A

to limit the level of reactive power exported from the generator. Primary

and secondary setting groups provide additional control for two distinct machine operating conditions. The
var limiter setpoint

B

is expressed as a percentage of the calculated, maximum VA rating for the machine.

A delay setting

C

establishes a time delay between when the var threshold is exceeded and the DECS-

250N acts to limit the var flow.

Var limiter settings are illustrated in Figure 52.

Figure 52. Var Limiter Settings

A

Var Limiter Enable: Select checkbox to enable var limiter.

B

Var Limiter Setpoint: Adjustable from 0 to 200% in 0.1% increments.

C

Var Limiter Delay: Adjustable from 0 to 300 s in 0.1 s increments.

Limiter Scaling

BESTCOMSPlus Navigation Path: Settings Explorer, Operating Settings, Limiters, Scaling

HMI Navigation Path: Settings, Operating Settings, Limiters, Scaling

Automatic adjustment (scaling) of the overexcitation limiter and stator current limiter is possible through
the DECS-250N auxiliary control input. Limiter scaling settings are illustrated in Figure 53. OEL and SCL
scaling may be independently enabled and disabled

A

. Automatic adjustment of the OEL and SCL is based

on six parameters: signal and scale for three points (levels).

With the scaling input set to Auxiliary Input, the signal value

B

for each point represents the auxiliary

control input. This input can be a 4 to 20 mAdc signal applied to terminals I+ and I– or a –10 to +10 Vdc
signal applied to terminals V+ and V–. (The input type is selected in BESTCOMSPlus). See the Auxiliary
Control
chapter of this manual for details.

With the scaling input set to AEM RTD #, the signal value for each point represents an AEM RTD input in
degrees Fahrenheit. See the Analog Expansion Module chapter of the manual for details.

The scale value

C

for each point defines the limiter low level as a percent of rated field current for the OEL

and rated stator current for the SCL.

This manual is related to the following products: