beautypg.com

Loss of sensing – Basler Electric DECS-250N User Manual

Page 60

background image

44

9440500990 Rev D

Protection

DECS-250N

Generator Overvoltage

An overvoltage pickup condition occurs when the sensed generator terminal voltage increases above the
pickup setting

A

. An overvoltage trip condition occurs if the generator voltage remains above the pickup

threshold for the duration of the time delay setting

B

. Generator overvoltage protection can be enabled and

disabled

C

without altering the pickup and time delay settings. Overvoltage pickup and trip elements in

BESTlogicPlus can be used in a logic scheme to initiate corrective action in response to the condition.
BESTCOMSPlus generator overvoltage settings are illustrated in Figure 29.

Figure 29. Generator Overvoltage Protection Settings

A

Generator Overvoltage Pickup (V): Adjustable from 0 to 600,000 Vac in 1 Vac increments.

B

Generator Overvoltage Time Delay (s): Adjustable from 0.1 to 60 seconds in 0.1 second increments.

C

Generator Overvoltage Enable/Disable: Select Enabled or Disabled.

Loss of Sensing

The generator voltage is monitored for a loss of sensing (LOS) condition. LOS protection settings are
illustrated in Figure 30.

In the DECS-250N, a loss of sensing event is calculated using sequence components. A loss of sensing
event occurs when the positive sequence voltage drops below the balanced

A

setting percentage of the

AVR setpoint, or when the negative sequence voltage increases above the unbalanced

B

setting

percentage of the positive sequence voltage. A delay timer

C

is started when the event occurs, delaying

the alarm by a predetermined time

A LOS condition can be used to initiate a transfer to manual (FCR) control mode

D

. It also can be

configured in BESTlogicPlus to initiate other actions. Protection can be enabled and disabled

E

without

altering the individual loss of sensing settings.

LOS protection is automatically disabled when a short circuit exists. A short circuit is detected when the
measured current is greater than twice the rated current for a single-phase CT connection and when the
positive sequence current is greater than twice the rated current for a three-phase CT connection.

Figure 30. Loss of Sensing Protection Settings

This manual is related to the following products: