BESTlogic

Plus

DECS-250N

Name

Description

Symbol

OEL DISABLED IN
MANUAL MODE

When true, this element disables OEL when
the unit is operating in Manual mode.

OEL ONLINE

When true, this element enables the use of
OEL when the unit is considered online.

OEL SELECT
SECONDARY
SETTINGS

When true, this element selects the secondary
settings for OEL.

PARALLEL ENABLE
LM

When true, this element informs the unit that it
is online. The element should be enabled
when the 52LM is closed.

This element also allows UEL and droop
compensation to operate when true.

PID SELECT
SECONDARY
SETTINGS

When true, this element selects secondary
settings on the PID.

PF/VAR ENABLE

When true, this element enables the PF and
Var controller, and informs the unit that it is
online. The Var/PF Selection element must be
set to true to use var or PF mode. This
element should be enabled when the 52JK is
closed.

PREPOSITION 1
ENABLE

When true, this element informs the unit to
use setpoints for Preposition 1.

PREPOSITION 2
ENABLE

When true, this element informs the unit to
use setpoints for Preposition 2.

PREPOSITION 3
ENABLE

When true, this element informs the unit to
use setpoints for Preposition 3.

PROTECTION
SELECT
SECONDARY
SETTINGS

When true, this element informs the unit to
use secondary values for protection.

PSS SEQ CNTRL
ENABLED

When true, PSS sequence (phase rotation)
control is enabled. (Available when the
controller is equipped with the optional Power
System Stabilizer, style number xPxxxxx)

PSS OUTPUT
DISABLE

When true, this element disables the output of
the PSS. The PSS continues to run, but the
output is not used. (Available when the
controller is equipped with the optional Power
System Stabilizer, style number xPxxxxx)