beautypg.com

Basler Electric DECS-250N User Manual

Page 51

background image

9440500990 Rev D

35

DECS-250N

Auxiliary Control

A

Input Type: Select Voltage or Current.

B

Input Function: Select DECS Input, Limiter Scaling, or PSS Test Input.

C

AVR (Mode) Gain: Adjustable from –99 to +99 in 0.01 increments.

D

FCR (Mode) Gain: Adjustable from –99 to +99 in 0.01 increments.

E

FVR (Mode) Gain: Adjustable from –99 to +99 in 0.01 increments.

F

Var (Mode) Gain: Adjustable from –99 to +99 in 0.01 increments.

G

PF (Mode) Gain: Adjustable from –99 to +99 in 0.01 increments.

H

Summing Type: Select Inner Loop or Outer Loop.

This manual is related to the following products: