Maximum Field Flash Time
Range ............................................... 1 to 50 s
Increment ......................................... 1 s
Voltage Matching
Accuracy........................................... Generator rms voltage is matched with the bus rms voltage to within
±0.5% of the generator voltage.
On-Line Overexcitation Limiting
High Current Level
Pickup
Range ............................................... 0 to 40 Adc
Increment ......................................... 0.1 Adc
Time
Range ............................................... 0 to 10 s
Increment ......................................... 1 s
Medium Current Level
Pickup
Range ............................................... 0 to 30 Adc
Increment ......................................... 0.1 Adc
Time
Range ............................................... 0 to 120 s
Increment ......................................... 1 s
Low Current Level
Pickup
Range ............................................... 0 to 20 Adc
Increment ......................................... 0.1 Adc
Off-Line Overexcitation Limiting
High Current Level
Pickup Range ................................... 0 to 40 Adc
Pickup Range Increment .................. 0.1 Adc
Time Delay Range ........................... 0 to 10 s
Time Delay Increment ...................... 1 s
Low Current Level
Pickup Range ................................... 0 to 20 Adc
Pickup Increment ............................. 0.1 Adc
Sequence of Events Recording (SER)2
Over 1,000 records are stored in nonvolatile memory (retrievable via BESTCOMSPlus
®
). The SER can be
triggered by: Input/Output status changes, system operating status changes, or alarm annunciations.