48

9440500990 Rev D

Protection

DECS-250N

Figure 35. Loss of Excitation Protection Settings

A

Pickup (% of rated vars): Adjustable from 0 to 150% in 1% increments.

B

Time Delay: Adjustable from 0 to 300 seconds in 0.1 second increments.

C

Mode: Select Disabled or Enabled.

Field Protection

BESTCOMSPlus Navigation Path: Settings Explorer, Protection, Field

HMI Navigation Path: Settings, Protection, Field

Field protection provided by the DECS-250N includes field overvoltage, field overcurrent, an exciter diode
monitor, and power input failure.

Field Overvoltage

A field overvoltage condition occurs when the field voltage exceeds the field overvoltage threshold

A

for the

duration of the field overvoltage time delay

B

. Field overvoltage protection can be enabled and disabled

C

without altering the pickup and time delay settings. Field overvoltage pickup and trip elements in
BESTlogicPlus can be used in a logic scheme to initiate corrective action in response to the condition.
BESTlogicPlus field overvoltage settings are illustrated in Figure 36.

Figure 36. Field Overvoltage Protection Settings

A

Field Overvoltage Pickup (V): Adjustable from 0 to 325 Vdc in 1 Vdc increments.

B

Field Overvoltage Time Delay (s): Adjustable from 0.2 to 30 seconds in 0.1 second increments.

C

Field Overvoltage Mode: Select Disabled or Enabled.

Field Overcurrent

A field overcurrent condition is annunciated when the field current exceeds the field overcurrent pickup
level

A

for the duration of the field overcurrent time delay. Depending on the selected timing mode

B

, the

time delay can be fixed or related to an inverse function. Definite timing mode uses a fixed time delay

C

. In

inverse timing mode, the time delay is shortened in relation to the level of field current above the pickup
level. The time dial

D

setting acts as a linear multiplier for the time to an annunciation. This enables the

DECS-250N to approximate the heating characteristic of the generator and generator step-up transformer