Rtd inputs – Basler Electric DECS-250N User Manual
Page 345
![background image](https://www.manualsdir.com/files/773924/content/doc345.png)
9440500990 Rev D
329
DECS-250N
Analog Expansion Module
Figure 177. Remote Analog Input Settings
A
Label Text: An alphanumeric character string with a maximum of 64 characters.
B
Input Type: Voltage or Current.
C
Hysteresis: Adjustable from 0 to 100% in 0.1% increments.
D
Arming Delay: Adjustable from 0 to 300 s in 1 s increments.
E
Stop Mode Inhibit: Yes or No.
F
Param Min: Adjustable from
–9999.0 to +9999.0 in increments of 0.1
G
Min Input Current: Adjustable from 4 to 20 mA in 0.1 mA increments.
H
Min Input Voltage: Adjustable from 0 to 10 V in 0.1 V increments.
I
Param Max: Adjustable from
–9999.0 to +9999.0 in increments of 0.1.
J
Max Input Current: Adjustable from 4 to 20 mA in 0.1 mA increments.
K
Max Input Voltage: Adjustable from 0 to 10 V in 0.1 V increments.
L
Mode: Disabled, Over, or Under.
M
Threshold: Adjustable from
–9999.0 to +9999.0 in increments of 0.1.
N
Activation Delay: Adjustable from 0 to 300 s in 1 s increments.
RTD Inputs
BESTCOMSPlus Navigation Path: Settings, Programmable Inputs, Remote RTD Inputs
HMI Navigation Path: Settings, Programmable Inputs, Remote RTD Inputs
The AEM-2020 provides eight user-configurable RTD inputs that can annunciate a latching or non-
latching alarm. The RTD inputs are always monitored and their status is displayed on the appropriate
metering screens. To make identifying the RTD inputs easier, a user-assigned name
A
can be given to
each input.
Select the amount of hysteresis
B
needed to prevent rapid switching of the alarm. Select the RTD type
C
. A
user-adjustable arming delay
D
allows configuration of the RTD input threshold monitoring in one of two
ways. (1) When the arming delay is set to zero, threshold monitoring is performed all the time, whether or
not excitation is enabled. (2) When the arming delay is set to a non-zero value, threshold monitoring
begins when the arming delay time has expired after system startup is complete. An out-of-range alarm,
configured on the Alarm Configuration, Alarms screen in BESTCOMSPlus, alerts the user of an open or