beautypg.com

Ethernet port – Basler Electric DECS-250N User Manual

Page 181

background image

9440500990 Rev D

165

DECS-250N

Communication

Figure 139. Typical RS-485 Connections

RS-485 port communication settings are illustrated in Figure 140 and consist of the baud rate

A

, number of

bits per character

B

, parity

C

, and the number of stop bits

D

.

Figure 140. RS-485 Port Communication Settings

A

Baud Rate: Select 1200, 2400, 4800, 9600, 19200, 38400, 57600, or 115200.

B

Bits Per Char: Select 7 or 8 bits/character.

C

Parity: Select Even, Odd, or No parity.

D

Stop Bits: Select 1 or 2 stop bits.

Ethernet Port

An Ethernet port uses the Modbus/TCP protocol for polled communication with other networked devices
or remote annunciation and control with an IDP-800 Interactive Display Panel.

P

0

0

7

1

-3

4

22

6

4

A

B

C

TO DECS-250N

TO RS-422/RS-485

DB-37 FEMALE

19

24

C

B

A

A

B

C

4000 ft

1219.2 m

maximum

DECS-250N

RS485

R

t

t

R

R = Optional terminating resistor
120 ohms, typical

t

DECS-250N

RS485

DECS-250N

RS485

This manual is related to the following products: