beautypg.com

Basler Electric DECS-250N User Manual

Page 78

background image

62

9440500990 Rev D

Limiters

DECS-250N

UEL operates in all regulation modes. UEL behavior in manual mode can be configured to limit excitation
or issue an alarm. This behavior is configured in BESTlogicPlus.

Note

For UEL to operate, the PARALLEL_EN_LM logic block must be set
true in BESTlogicPlus programmable logic.

UEL settings are illustrated in Figure 48 and Figure 49.

Underexcitation limiting is implemented through an internally-generated UEL curve or a user-defined UEL
curve

B

. The internally-generated curve is based on the desired reactive power limit at zero real power with

respect to the generator voltage and current rating. The absorbed reactive power axis of the curve on the
UEL Custom Curve screen can be tailored

C

for your application.

A user-defined curve can have a maximum of five points

D

. This curve allows the user to match a specific

generator characteristic by specifying the coordinates of the intended leading reactive power (kvar) limit at
the appropriate real power (kW) level.

The levels entered for the user-defined curve are defined for operation at the rated generator voltage. The
user-defined UEL curve can be automatically adjusted based on generator operating voltage by using the
UEL voltage dependency real-power exponent

E

. The user-defined UEL curve is automatically adjusted

based on the ratio of the generator operating voltage divided by the generator rated voltage raised to the
power of the UEL voltage dependency real-power exponent. UEL voltage dependency is further defined
by a real power filter time constant

F

that is applied to the low-pass filter for the real power output.

Figure 48. UEL Configuration Settings

This manual is related to the following products: