176
9440500990 Rev D
Configuration
DECS-250N
Figure 153. Device Information
A
Application Part Number: Read-only field indicates the firmware file part number.
B
Application Version: Read-only field indicates the firmware version number.
C
Application Build Date: Read-only field indicates the release date of the device firmware.
D
Boot Code Version: Read-only field indicates the version of hardware boot code.
E
Application Version Number: When configuring settings offline, select the appropriate firmware version
to ensure settings/features compatibility with the DECS-250N.
F
Model Number: Read-only field displays the product model number.
G
Serial Number: Read-only field displays the serial number of the product.
H
Device ID: Enter up to 60 alphanumeric characters.
Display Units
BESTCOMSPlus Navigation Path: General Settings, Display Units
HMI Navigation Path: N/A
When working with DECS-250N settings in BESTCOMSPlus, you have the option of viewing the settings
in English or Metric
A
units and as primary units or per-unit values
B
. When per-unit values are selected,
settings are entered as per-unit values and BESTCOMSPlus converts the per-unit inputs to high-side
values based on the generator rated data. The display units setting is illustrated in Figure 154 and is not
available for settings shown on the front panel display.