Specifications

DECS-250N

DC Input
Nominal Input ................................... 125 Vdc
Input Range ...................................... 90 to 150 Vdc
Burden .............................................. 30 W

Terminals

AC Input ........................................... L, N
DC Input ........................................... BATT+, BATT–

Generator and Bus Voltage Sensing

Type ................................................. 1-phase or 3-phase–3-wire
Burden .............................................. <1 VA per phase

Terminals

Generator Voltage Sensing .............. E1, E2, E3
Bus Voltage Sensing ........................ B1, B2, B3

50 Hz Sensing Voltage Nominal Input, Range

100 Vac ............................................ 90 to 110 Vac
200 Vac ............................................ 180 to 220 Vac
400 Vac ............................................ 360 to 440 Vac

60 Hz Sensing Voltage Nominal Input, Range

120 Vac ............................................ 108 to 132 Vac
240 Vac ............................................ 216 to 264 Vac
480 Vac ............................................ 432 to 528 Vac
600 Vac ............................................ 540 to 660 Vac

Generator Current Sensing

Configuration .................................... 4 inputs: A-, B-, C-phase, and cross-current compensation CT input
Type ................................................. 1-phase (B-phase), 1-phase with cross-current compensation, 3-

phase, 3-phase with cross-current compensation

Range ............................................... 1 Aac or 5 Aac nominal
Frequency ........................................ 50/60 Hz

Burden

1 Aac Sensing .................................. <5 VA
5 Aac Sensing .................................. <10 VA

Terminals

A-Phase............................................ CTA+, CTA–
B-Phase............................................ CTB+, CTB–
C-Phase ........................................... CTC+, CTC–
Cross-Current Compensation .......... CCCT+, CCCT–