68

9440500990 Rev D

Limiters

DECS-250N

Figure 56. Underfrequency/Volts per Hertz Limiter Settings

A

Limiter Mode: Select UF Limiter or V/Hz Limiter.

B

Underfrequency Limiter Corner Frequency: Adjustable from 40 to 75 Hz in 0.1 Hz increments.

C

Underfrequency Limiter Slope: Adjustable from 0 to 3 in increments of 0.01.

D

V/Hz High Limiter: Adjustable from 0 to 3 in increments of 0.01.

E

V/Hz Low Limiter: Adjustable from 0 to 3 in increments of 0.01.

F

V/Hz Time Limiter: Adjustable from 0 to 10 s in 0.2 s increments.


This manual is related to the following products: