Can communication, Connections, Port configuration – Basler Electric DECS-250N User Manual

Page 182: Remote module setup

background image

166

9440500990 Rev D

Communication

DECS-250N

CAN Communication

BESTCOMSPlus Navigation Path: Settings Explorer, Communications, CAN Bus, CAN Bus Setup

HMI Navigation Path: Settings, Communications, CAN Bus, CAN Bus Setup

One CAN (controller area network) interface (CAN 1) facilitates communication between the DECS-250N
and optional modules such as the contact expansion module (CEM-2020) and analog expansion module
(AEM-2020).

A second CAN interface (CAN 2) enables the DECS-250N to provide generator and system parameters
to a generator controller such as the Basler DGC-2020. CAN 2 also permits DECS-250N setpoint and
mode control from an external device connected to the CAN.

Both CAN bus interfaces utilize the SAE J1939 messaging protocol.

DECS-250N CAN parameters are listed and defined in the CAN Communication chapter of this manual.

Connections

DECS-250N CAN connections should be made with twisted-pair, shielded cable. Each CAN port
(designated CAN 1 and CAN 2) has a CAN high (H) terminal, a CAN low (L) terminal, and a CAN drain
(SH) terminal. CAN port terminals are illustrated in the Terminals and Connectors chapter of this manual.

Port Configuration

Each DECS-250N CAN port must be identified by a unique address number

A

. The baud rate

B

of each port

can be configured for 125 kbps or 250 kbps. Port configuration settings are illustrated in Figure 141.

Figure 141. CAN Port Configuration Settings

A

CAN bus Address: Adjustable from 1 to 253.

B

Baud Rate: Select 125 kbps or 250 kbps.

Remote Module Setup

BESTCOMSPlus Navigation Path: Settings Explorer, Communications, CAN Bus, Remote Module
Setup
HMI Navigation Path: Settings, Communications, CAN Bus, Remote Module Setup

Optional, external modules, such as the contact expansion module (CEM-2020) and analog expansion
module (AEM-2020), communicate via the DECS-250N CAN 1 interface and are configured through the
DECS-250N BESTCOMSPlus interface. These settings are illustrated in Figure 142.

Contact Expansion Module

When enabled

A

for operation, the CEM-2020 CAN address

B

is assigned a unique number and the number

of outputs

C

is selected. Standard module (CEM-2020) provides 24 output contacts and high-current

module (CEM-2020H) provides 18 output contacts.

Analog Expansion Module

When enabled

D

for operation, the AEM-2020 CAN address

E

is assigned a unique address for

communication on the network.