Metering, Analog inputs – Basler Electric DECS-250N User Manual
Page 348

332
9440500990 Rev D
Analog Expansion Module
DECS-250N
Figure 180. Remote Analog Output Settings
A
Parameter Selection: Gen VAB, Gen VBC, Gen VCA, Gen V Average, Bus Freq, Bus VAB, Bus VBC,
Bus VCA, Gen Freq, Gen PF, kWh, kvarh, Gen IA, Gen IB, Gen IC, Gen I Average, kW Total, kVA Total,
kvar Total, EDM Ripple, Exciter Field Voltage, Exciter Field Current, Auxiliary Input Voltage, Auxiliary
Input Current, Setpoint Position, Tracking Error, Negative Sequence Voltage, Negative Sequence
Current, Positive Sequence Voltage, Positive Sequence Current, PSS Output, Analog Input 1-8, RTD
Input 1-8, Thermocouple 1-2, Power Input, or NLS Error Percent.
B
Output Type: Voltage or Current.
C
Out of Range Activation Delay: Adjustable from 0 to 300 s in 1 s increments.
D
Param Min: Adjustable from
–999,999.0 to +999,999.0 in increments of 0.1.
E
Min Output Current: Adjustable from 4 to 20 mA in 0.1 mA increments.
F
Min Output Voltage: Adjustable from 0 to 10 V in 0.1 V increments.
G
Param Max: Adjustable from
–999,999.0 to +999,999.0 in increments of 0.1.
H
Max Output Current: Adjustable from 4 to 20 mA in 0.1 mA increments.
I
Max Output Voltage: Adjustable from 0 to 10 V in 0.1 V increments.
Metering
Analog Inputs
BESTCOMSPlus Navigation Path: Metering, Status, Inputs, Remote Analog Inputs
HMI Navigation Path: Metering, Status, Inputs, Remote Analog Input Values
The value and status of the remote analog inputs are shown on this screen. The status is TRUE when the
corresponding LED is green. Refer to Figure 181. Remote Analog Input #1 is shown.
Figure 181. Remote Analog Inputs Metering