Basler Electric DECS-250N User Manual
Page 255
9440500990 Rev D
239
DECS-250N
Modbus™ Communication
Name
Register
Type
Byte
s
R/W
Unit
Range
Index into Table of Gain Constants
47861
Float
4
R W
n/a
1 - 21
Primary AVR Mode Proportional Gain
47863
Float
4
R W
n/a
0 - 1000
Primary AVR Mode Integral Gain
47865
Float
4
R W
n/a
0 - 1000
Primary AVR Mode Derivative Gain
47867
Float
4
R W
n/a
0 - 1000
OEL Integral Gain: Ki
47869
Float
4
R W
n/a
0 - 1000
PF Mode Integral Gain: Ki
47871
Float
4
R W
n/a
0 - 1000
Var Mode Integral Gain: Ki
47873
Float
4
R W
n/a
0 - 1000
FCR Mode Loop Gain: Ka
47875
Float
4
R W
n/a
0 - 1000
Primary AVR Mode Loop Gain: Ka
47877
Float
4
R W
n/a
0 - 1000
Var Mode Loop Gain: Kg
47879
Float
4
R W
n/a
0 - 1000
PF Mode Loop Gain: Kg
47881
Float
4
R W
n/a
0 - 1000
OEL Loop Gain: Kg
47883
Float
4
R W
n/a
0 - 1000
UEL Loop Gain: Kg
47885
Float
4
R W
n/a
0 - 1000
UEL Integral Gain: Ki
47887
Float
4
R W
n/a
0 - 1000
Voltage Matching Loop Gain: Kg
47889
Float
4
R W
n/a
0 - 1000
Primary AVR Mode Derivative Time Constant:
Td
47891
Float
4
R W
n/a
0 - 1
Secondary Gain Option Index
47893
Uint32
4
R W
n/a
T'do=1.0 Te=0.17=1 T'do=1.5
Te=0.25=2 T'do=2.0 Te=0.33=3
T'do=2.5 Te=0.42=4 T'do=3.0
Te=0.50=5 T'do=3.5 Te=0.58=6
T'do=4.0 Te=0.67=7 T'do=4.5
Te=0.75=8 T'do=5.0 Te=0.83=9
T'do=5.5 Te=0.92=10 T'do=6.0
Te=1.00=11 T'do=6.5
Te=1.08=12 T'do=7.0
Te=1.17=13 T'do=7.5
Te=1.25=14 T'do=8.0
Te=1.33=15 T'do=8.5
Te=1.42=16 T'do=9.0
Te=1.50=17 T'do=9.5
Te=1.58=18 T'do=10.0
Te=1.67=19 T'do=10.5
Te=1.75=20 Custom=21
Secondary AVR Mode Proportional Gain - Kp
47895
Float
4
R W
n/a
0 - 1000
Secondary AVR Mode Integral Gain - Ki
47897
Float
4
R W
n/a
0 - 1000
Secondary AVR Mode Derivative Gain - Kd
47899
Float
4
R W
n/a
0 - 1000
Secondary AVR Mode Loop Gain - Kg
47901
Float
4
R W
n/a
0 - 1000
Secondary AVR Derivative Time Constant -
Td
47903
Float
4
R W
n/a
0 - 1
Active Gain Setting Group
47905
Uint16
2
R
n/a
n/a
SCL Loop Gain - Kg
47906
Float
4
R W
n/a
0 - 1000
SCL Integral Gain - Ki
47908
Float
4
R W
n/a
0 - 1000
Reserved 14
47910-
920
C9 Filler
22
n/a
n/a
n/a
Field Overvoltage Level
47921
Float
4
R W
Volt
Disabled=0, 1 - 325
Field Overcurrent Base Level
47923
Float
4
R W
Amp
Disabled=0, 0 - 22
Stator Undervoltage Level
47925
Float
4
R W
Volt
Disabled=0, 1 - 600000
Stator Overvoltage Level
47927
Float
4
R W
Volt
Disabled=0, 0 - 600000
Field Overvoltage Delay
47929
Float
4
R W
Millisecond
Disabled=0, 200 - 30000
Overcurrent Delay
47931
Float
4
R W
Millisecond
Disabled=0, 5000 - 60000
Stator Undervoltage Delay
47933
Float
4
R W
Millisecond
100 - 60000
Stator Overvoltage Delay
47935
Float
4
R W
Millisecond
100 - 60000
Field Overvoltage Alarm Enable
47937
Uint16
2
R W
n/a
Disabled=0 Enabled=1
Field Overcurrent Alarm Enable
47938
Uint16
2
R W
n/a
Disabled=0 Enabled=1
Stator Undervoltage Alarm Enable
47939
Uint16
2
R W
n/a
Disabled=0 Enabled=1
Stator Overvoltage Alarm Enable
47940
Uint16
2
R W
n/a
Disabled=0 Enabled=1