Setpoints, Table 29. setpoint group parameters – Basler Electric DECS-250N User Manual

Page 241

background image

9440500990 Rev D

225

DECS-250N

Modbus™ Communication

Name

Register

Type

Bytes

R/W

Unit

Range

UEL Secondary Curve Y5

41828

Float

4

R W

kilovar

0 – 1.5 • Rated kVA

SCL Primary Reference Hi

41830

Float

4

R W

Amp

0 - 66000

SCL Primary Reference Lo

41832

Float

4

R W

Amp

0 - 66000

SCL Primary Time Hi

41834

Float

4

R W

Second

0 - 60

SCL Primary No Response Time

41836

Float

4

R W

Second

0 - 10

SCL Secondary Reference Hi

41838

Float

4

R W

Amp

0 - 66000

SCL Secondary Reference Lo

41840

Float

4

R W

Amp

0 - 66000

SCL Secondary Time Hi

41842

Float

4

R W

Second

0 - 60

SCL Secondary No Response Time

41844

Float

4

R W

Second

0 - 10

SCL Scale Enable

41846

Uint32

4

R W

n/a

Disabled=0
Auxiliary Input=1
AEM RTD 1=2
AEM RTD 2=3
AEM RTD 3=4
AEM RTD 4=5
AEM RTD 5=6
AEM RTD 6=7
AEM RTD 7=8
AEM RTD 8=9

SCL Scale Signal 1

41848

Float

4

R W

Limiter
Scale
Volt
or Deg F

Adjustment range is determined by register
41846.
-10 – 10 V when 41846 = 1
-58 – 482°F when 41846 = 2-8

SCL Scale Signal 2

41850

Float

4

R W

Limiter
Scale
Volt
or Deg F

Adjustment range is determined by register
41846.
-10 – 10 V when 41846 = 1
-58 – 482°F when 41846 = 2-8

SCL Scale Signal 3

41852

Float

4

R W

Limiter
Scale
Volt
or Deg F

Adjustment range is determined by register
41846.
-10 – 10 V when 41846 = 1
-58 – 482°F when 41846 = 2-8

SCL Scale Point 1

41854

Float

4

R W

Percent

0 - 200

SCL Scale Point 2

41856

Float

4

R W

Percent

0 - 200

SCL Scale Point 3

41858

Float

4

R W

Percent

0 - 200

Var Limit Enable

41860

Uint32

4

R W

n/a

Disabled=0 Enabled=1

Var Limit Primary Delay

41862

Float

4

R W

Second

0 - 300

Var Limit Primary Setpoint

41864

Float

4

R W

Percent

0 - 200

Var Limit Secondary Delay

41866

Float

4

R W

Second

0 - 300

Var Limit Secondary Setpoint

41868

Float

4

R W

Percent

0 - 200

Var Limit Enable Status

41870

Uint32

4

R

n/a

Off=0 On=1

OEL Primary Takeover Reset Time
Coefficient Off

41872

Float

4

R W

n/a

0.01 – 100

OEL Primary Takeover Reset Time
Coefficient On

41874

Float

4

R W

n/a

0.01 – 100

OEL Secondary Takeover Reset Time
Coefficient Off

41876

Float

4

R W

n/a

0.01 – 100

OEL Secondary Takeover Reset Time
Coefficient On

41878

Float

4

R W

n/a

0.01 – 100

OEL Primary Takeover Reset Type Off

41880

Uint32

4

R W

n/a

Inverse=0,Integrating=1,Instantaneous=2

OEL Primary Takeover Reset Type On

41882

Uint32

4

R W

n/a

Inverse=0,Integrating=1,Instantaneous=2

OEL Secondary Takeover Reset Type Off

41884

Uint32

4

R W

n/a

Inverse=0,Integrating=1,Instantaneous=2

OEL Secondary Takeover Reset Type On

41886

Uint32

4

R W

n/a

Inverse=0,Integrating=1,Instantaneous=2

Setpoints

Table 29. Setpoint Group Parameters

Name

Register

Type

Bytes

R/W

Unit

Range

Field Current Regulation Setpoint

42200

Float

4

R W

Amp

Setpoint adjustment range determined
by registers 42212 and 42214.

Field Current Regulation Traverse Rate

42202

Float

4

R W

Second

10 – 200