Basler Electric DECS-250N User Manual
Page 312
296
9440500990 Rev D
PROFIBUS Communication
DECS-250N
Instance Name
Inst. #
Type
RW
Key Name
Unit
Range
Remote RTD In 8
234
Float
R/W
Threshold 4
Activation Delay GG
Sec
0 - 300
Remote TC In 1
235
UINT32 R/W
Stop Mode Inhibit GG
No
Unit
NO=0 YES=1
Remote TC In 1
235
UINT32 R/W
Threshold 1 Type GG
No
Unit
Disabled=0 Over=1 Under=2
Remote TC In 1
235
UINT32 R/W
Threshold 2 Type GG
No
Unit
Disabled=0 Over=1 Under=2
Remote TC In 1
235
UINT32 R/W
Threshold 3 Type GG
No
Unit
Disabled=0 Over=1 Under=2
Remote TC In 1
235
UINT32 R/W
Threshold 4 Type GG
No
Unit
Disabled=0 Over=1 Under=2
Remote TC In 1
236
Float
R/W
Cal Offset GG
Deg F
-99999 - 99999
Remote TC In 1
236
Float
R/W
Hysteresis GG
%
0 - 100
Remote TC In 1
236
Float
R/W
Arming Delay GG
Sec
0 - 300
Remote TC In 1
236
Float
R/W
Threshold 1 Pickup GG
Deg F
32 - 2507
Remote TC In 1
236
Float
R/W
Threshold 1
Activation Delay GG
Sec
0 - 300
Remote TC In 1
236
Float
R/W
Threshold 2 Pickup GG
Deg F
32 - 2507
Remote TC In 1
236
Float
R/W
Threshold 2
Activation Delay GG
Sec
0 - 300
Remote TC In 1
236
Float
R/W
Threshold 3 Pickup GG
Deg F
32 - 2507
Remote TC In 1
236
Float
R/W
Threshold 3
Activation Delay GG
Sec
0 - 300
Remote TC In 1
236
Float
R/W
Threshold 4 Pickup GG
Deg F
32 - 2507
Remote TC In 1
236
Float
R/W
Threshold 4
Activation Delay GG
Sec
0 - 300
Remote TC In 2
237
UINT32 R/W
Stop Mode Inhibit GG
No
Unit
NO=0 YES=1
Remote TC In 2
237
UINT32 R/W
Threshold 1 Type GG
No
Unit
Disabled=0 Over=1 Under=2
Remote TC In 2
237
UINT32 R/W
Threshold 2 Type GG
No
Unit
Disabled=0 Over=1 Under=2
Remote TC In 2
237
UINT32 R/W
Threshold 3 Type GG
No
Unit
Disabled=0 Over=1 Under=2
Remote TC In 2
237
UINT32 R/W
Threshold 4 Type GG
No
Unit
Disabled=0 Over=1 Under=2
Remote TC In 2
238
Float
R/W
Cal Offset GG
Deg F
-99999 - 99999
Remote TC In 2
238
Float
R/W
Hysteresis GG
%
0 - 100
Remote TC In 2
238
Float
R/W
Arming Delay GG
Sec
0 - 300
Remote TC In 2
238
Float
R/W
Threshold 1 Pickup GG
Deg F
32 - 2507
Remote TC In 2
238
Float
R/W
Threshold 1
Activation Delay GG
Sec
0 - 300
Remote TC In 2
238
Float
R/W
Threshold 2 Pickup GG
Deg F
32 - 2507
Remote TC In 2
238
Float
R/W
Threshold 2
Activation Delay GG
Sec
0 - 300