Modbus™ Communication

Name

Register

Type

Byte

s

R/W

Unit

Range

Annunciation Status Bit Flags 1

47303

Uint16

2

R

n/a

(0 = clear, 1 = annunciation
present): b0 = field overvoltage,
b1 = field overcurrent, b2 = gen.
undervoltage, b3 = gen.
overvoltage, b4 =
underfrequency, b5 = in OEL, b6
= in UEL, b7 = in FCR,
b8 = loss of sensing voltage, b9 =
setpoint at lower limit, b10 =
setpoint at upper limit, b11 = gen.
failed to build up, b12 = gen.
below 10Hz,
b13 = unassigned, b14 = exciter
diode open, b15 = exciter diode
shorted

Reserved 3

47304

Float

4

R

n/a

n/a

Protection Status Bit Flags 2

47306

Uint16

2

R

n/a

(0 = clear, 1 = condition present)
b0 = loss of field, b1 = in SCL, b2
– b15 are unassigned

Annunciation Status Bit Flags 2

47307

Uint16

2

R

n/a

(0 = clear, 1 = condition present)
b0 = loss of field, b1 = in SCL, b2
– b15 are unassigned

Reserved 4

47308-
375

C2 Filler

136

n/a

n/a

n/a

Reserved 5

47376-
499

C3 Filler

248

n/a

n/a

n/a

Auxiliary Input Function

47500

Uint16

2

n/a

n/a

DECS Input=0 PSS Test Input=1
Limiter Selection=2

Generator Rated Frequency

47501

Uint32

4

R W

n/a

50 Hz=50 60 Hz=60

Generator PT Primary Voltage Rating

47503

Float

4

R W

n/a

1 - 500000

Generator PT Secondary Voltage Rating

47505

Float

4

R W

n/a

1 - 600

Generator CT Primary Current Rating

47507

Float

4

R W

n/a

1 - 99999

Generator CT Secondary Current Rating

47509

Int32

4

R W

n/a

1=1 5=5

Not used in DECS-250N

47511

Float

4

R W

n/a

Reserved Float 1

47513

Float

4

R

n/a

0 - 10000

Bus Sensing PT Primary Rating

47515

Float

4

R W

n/a

1 - 500000

Bus Sensing PT Secondary Rating

47517

Float

4

R W

n/a

1 - 600

Reserved 6

47519

Float

4

R

n/a

n/a

Reserved 7

47521

Float

4

R

n/a

n/a

Generator Rated Voltage

47523

Float

4

R W

Volt

1 - 500000

Generator Rated Current

47525

Float

4

R

Amp

0 – 180000

Generator Rated Field Voltage

47527

Float

4

R W

Volt

1 – 250 if the unit is a DECS-
250N with power configuration
style #3.

Generator Rated Field Current

47529

Float

4

R W

Amp

1 – 20

Nominal Bus Voltage

47531

Float

4

R W

Volt

1 - 500000

Auxiliary Input Gain for AVR Mode

47533

Float

4

R W

n/a

-99 – 99

Time Delay Before Autotracking

47535

Float

4

R W

Second

0 – 8

Traverse Rate of Autotracking

47537

Float

4

R W

Second

1 – 80

Not used in DECS-250N

47539

Float

4

R W

n/a

Gain for Cross Current Compensation

47541

Float

4

R W

Percent

-30 – 30

Sensing Mode

47543

Uint16

2

R W

1-phase (A-C)=0 3-phase=1

Auxiliary Input Summing Mode

47544

Uint16

2

R W

Voltage=0 Var=1

Not used in DECS-250N

47545

Uint16

2

R

n/a

n/a

Reserved 8

47546

Uint16

2

R

n/a

n/a

Auxiliary Input Mode

47547

Uint16

2

R W

Voltage=0 Current=1

For Future Use

47548

Uint16

2

R

n/a

n/a

External Tracking Time Delay

47549

Float

4

R W

Second

0 - 8

External Tracking Traverse Rate

47551

Float

4

R W

Second

1 – 80