Basler Electric DECS-250N User Manual
Page 237
![background image](https://www.manualsdir.com/files/773924/content/doc237.png)
9440500990 Rev D
221
DECS-250N
Modbus™ Communication
Group
Name
Register
Type
Bytes
R/W
Unit
Range
Energy Meter
Negative varhour total
41336
Float
4
RW
VArHour
-1.00E+09 -
0.00E+00
Energy Meter
VA hour total
41338
Float
4
RW
VAHour
0.00E+00 -
1.00E+09
Sync Meter 1
Slip Angle
41340
Float
4
R
Degree
-359.9 – 359.9
Sync Meter 1
Slip Frequency
41342
Float
4
R
Hertz
n/a
Sync Meter 1
Voltage Difference
41344
Float
4
R
Volt
n/a
Generator Frequency Meter
1
Frequency
41346
Float
4
R
Hertz
10 - 180
Bus Frequency Meter 1
Frequency
41348
Float
4
R
Hertz
10 - 180
Auxiliary Input Voltage 1
Value
41350
Float
4
R
Volt
-9999999 -
9999999
Auxiliary Input Current 1
Value
41352
Float
4
R
Amp
-9999999 -
9999999
AEM Metering
RTD Input 1 Raw Value
41354
Float
4
R
Ohm
n/a
AEM Metering
RTD Input 2 Raw Value
41356
Float
4
R
Ohm
n/a
AEM Metering
RTD Input 3 Raw Value
41358
Float
4
R
Ohm
n/a
AEM Metering
RTD Input 4 Raw Value
41360
Float
4
R
Ohm
n/a
AEM Metering
RTD Input 5 Raw Value
41362
Float
4
R
Ohm
n/a
AEM Metering
RTD Input 6 Raw Value
41364
Float
4
R
Ohm
n/a
AEM Metering
RTD Input 7 Raw Value
41366
Float
4
R
Ohm
n/a
AEM Metering
RTD Input 8 Raw Value
41368
Float
4
R
Ohm
n/a
AEM Metering
RTD Input 1 Scaled Value
41370
Float
4
R
Deg F
-40000 -
9999999
AEM Metering
RTD Input 2 Scaled Value
41372
Float
4
R
Deg F
-40000 -
9999999
AEM Metering
RTD Input 3 Scaled Value
41374
Float
4
R
Deg F
-40000 -
9999999
AEM Metering
RTD Input 4 Scaled Value
41376
Float
4
R
Deg F
-40000 -
9999999
AEM Metering
RTD Input 5 Scaled Value
41378
Float
4
R
Deg F
-40000 -
9999999
AEM Metering
RTD Input 6 Scaled Value
41380
Float
4
R
Deg F
-40000 -
9999999
AEM Metering
RTD Input 7 Scaled Value
41382
Float
4
R
Deg F
-40000 -
9999999
AEM Metering
RTD Input 8 Scaled Value
41384
Float
4
R
Deg F
-40000 -
9999999
DECS Regulator Meter
Control Output
41386
Float
4
R
Percent
n/a
AEM Metering
RTD Input 1 Metric Value
41388
Float
4
R
Deg C
n/a
AEM Metering
RTD Input 2 Metric Value
41390
Float
4
R
Deg C
n/a
AEM Metering
RTD Input 3 Metric Value
41392
Float
4
R
Deg C
n/a
AEM Metering
RTD Input 4 Metric Value
41394
Float
4
R
Deg C
n/a
AEM Metering
RTD Input 5 Metric Value
41396
Float
4
R
Deg C
n/a
AEM Metering
RTD Input 6 Metric Value
41398
Float
4
R
Deg C
n/a
AEM Metering
RTD Input 7 Metric Value
41400
Float
4
R
Deg C
n/a
AEM Metering
RTD Input 8 Metric Value
41402
Float
4
R
Deg C
n/a
AEM Metering
Thermocouple Input 1 Metric
Value
41404
Float
4
R
Deg C
n/a
AEM Metering
Thermocouple Input 2 Metric
Value
41406
Float
4
R
Deg C
n/a
DECS Regulator Meter
NLS Error Percent
41408
Float
4
R
Percent
n/a
DECS Regulator Meter
Current Magnitude Pickup
41410
Float
4
R
n/a
-10 - 10
DECS Regulator Meter
NLS Current Magnitude Average
Pickup
41412
Float
4
R
n/a
-10 - 10
DECS Regulator Meter
NLS Number of Generators
Online
41414
Int32
4
R
n/a
n/a