Name

Description

Symbol

PSS SEQ CNTRL
SELECTION

When true, phase rotation is selected to be
ACB. False when phase rotation is selected to
be ABC. (Available when the controller is
equipped with the optional Power System
Stabilizer, style number xPxxxxx)

PSS MOTOR

When true, the PSS is in motor mode. False
when in generator mode. (Available when the
controller is equipped with the optional Power
System Stabilizer, style number xPxxxxx)

PSS SELECT
SECONDARY
SETTINGS

When true, this element selects secondary
settings for the PSS. (Available when the
controller is equipped with the optional Power
System Stabilizer, style number xPxxxxx)

RAISE ENABLE

When true, this element raises the active
setpoint.

SCL SELECT
SECONDARY
SETTINGS

When true, this element selects the secondary
settings for SCL.

SOFT START
SELECT
SECONDARY
SETTINGS

When true, this element selects the secondary
settings for softstart.

START ENABLE

When true, this element starts the unit.

STOP ENABLE

When true, this element stops the unit.

Transfer Watchdog
Trip

When true, this element opens the transfer
watchdog output.

UEL DISABLED IN
MANUAL MODE

When true, this element disables UEL when
the unit is operating in Manual mode.

UEL SELECT
SECONDARY
SETTINGS

When true, this element selects secondary
settings for UEL.

USER
PROGRAMMABLE
ALARM 1 - 16

When true, this element triggers a
programmable alarm.