9440500990 Rev D

175

DECS-250N

Configuration

The field flash dropout level

C

determines the level of generator voltage where field flashing is withdrawn.

In AVR mode, the field flash dropout level is expressed as a percentage of the generator terminal voltage.
In FCR mode, the level is expressed as a percentage of the field current. And in FVR mode, the level is
expressed as a percentage of the field voltage.

The field flash time

D

defines the maximum length of time that field flashing may be applied during startup.

To use the field flashing function, one of the DECS-250N programmable contact outputs must be
configured as a field flashing output.

Figure 152. Startup Function Settings

A

Soft Start Level (%): Adjustable from 0 to 90% in 1% increments.

B

Soft Start Time (s): Adjustable from 1 to 7,200 seconds in 1 second increments.

C

Field Flash Dropout Level: Adjustable from 0 to 100% in 1% increments.

D

Maximum Field Flash Time: Adjustable from 1 to 50 seconds in 1 second increments.

Device Information

BESTCOMSPlus Navigation Path: Settings Explorer, General Settings, Device Info

HMI Navigation Path: Settings, General Settings, Device Information, DECS-250N

Device information includes user-assigned identification labeling and read-only firmware version
information and product information. Device information (Figure 153) is provided for the DECS-250N,
CEM-2020 Contact Expansion Module, and AEM-2020 Analog Expansion Module.

Firmware and Product Information

Firmware and product information can be viewed on the HMI display and Device Info tab of
BESTCOMSPlus

®

.

Firmware Information

Firmware information is provided for the DECS-250N, optional CEM-2020, and optional AEM-2020. This
information includes the application part number

A

, version number

B

, and build date

C

. Also included is the

version of the boot code

D

. When configuring settings in BESTCOMSPlus while disconnected from a

DECS-250N, an Application Version Number setting

E

is available to ensure compatibility between the

selected settings and the actual settings available in the DECS-250N.

Product Information

Product information for the DECS-250N, CEM-2020, and AEM-2020 includes the device model number

F

and serial number

G

.

Device Identification

The user-assigned Device ID

H

can be used to identify DECS-250N controllers in reports and during

polling.