Limiters

Figure 47. Takeover OEL Settings

A

OEL Enable: Select checkbox to enable OEL.

B

OEL Mode: Select Summing Point or Takeover.

C

Summing Point OEL Offline Low Level: Adjustable from 0 to 20 Adc. The setting increment is 0.01 Adc.

D

Summing Point OEL Offline High Level: Adjustable from 0 to 40 Adc. The setting increment is 0.01 Adc.

E

Summing Point OEL Offline High Time: Adjustable from 0 to 10 s in 1 s increments.

F

Summing Point OEL Online Low Level: Adjustable from 0 to 20 Adc. The setting increment is 0.01 Adc.

G

Summing Point OEL Online Medium Level: Adjustable from 0 to 30 Adc. The setting increment is 0.01

Adc.

H

Summing Point OEL Online Medium Time: Adjustable from 0 to 120 s in 1 s increments.

I

Summing Point OEL Online High Level: Adjustable from 0 to 40 Adc for the DECS-250. The setting

increment is 0.01 Adc.

J

Summing Point OEL Online High Time: Adjustable from 0 to 10 s in 1 s increments.

K

dv/dt Enable: Check box to enable OEL voltage dependency.

L

dv/dt Level: Adjustable from –10 to 0 in 0.1 increments (per unit).

M

Takeover OEL Low Level: Adjustable from 0 to 15 Adc in increments of 0.01 Adc.

N

Takeover OEL High Level: Adjustable range varies depending on value of Low Level setting.

O

Takeover OEL Time Dial: Adjustable from 0.1 to 20 in increments of 0.1.

P

Reset Method: Select Inverse, Integrating, or Instantaneous.

Q

Reset Coefficient: Adjustable from 0.01 to 100 in increments of 0.01.

F

Takeover OEL curve.

G

Curve display selections/legend.

Underexcitation Limiter

BESTCOMSPlus Navigation Path: Settings Explorer, Operating Settings, Limiters, UEL

HMI Navigation Path: Settings, Operating Settings, Limiters, UEL

Operating a generator in an underexcited condition can cause the stator end iron to overheat. Extreme
underexcitation may lead to a loss of synchronism. The underexcitation limiter (UEL) senses the leading
var level of the generator and limits decreases in excitation to limit end-iron heating. When enabled