Basler Electric DECS-250N User Manual

Page 242

background image

226

9440500990 Rev D

Modbus™ Communication

DECS-250N

Name

Register

Type

Bytes

R/W

Unit

Range

Field Current Regulation Pre-position
Mode 1

42204

Uint32

4

R W

n/a

Maintain=0 Release=1

Field Current Regulation Pre-position 1

42206

Float

4

R W

Amp

Setpoint adjustment range determined
by registers 42212 and 42214.

Field Current Regulation Pre-position
Mode 2

42208

Uint32

4

R W

n/a

Maintain=0 Release=1

Field Current Regulation Pre-position 2

42210

Float

4

R W

Amp

Setpoint adjustment range determined
by registers 42212 and 42214.

Field Current Regulation Minimum
Setpoint Limit

42212

Float

4

R W

Percent

0 – 120

Field Current Regulation Maximum
Setpoint Limit

42214

Float

4

R W

Percent

0 – 120

Generator Voltage Setpoint

42216

Float

4

R W

Volt

Setpoint adjustment range determined
by registers 42228 and 42230.

Generator Voltage Traverse Rate

42218

Float

4

R W

Second

10 – 200

Generator Voltage Pre-position Mode 1

42220

Uint32

4

R W

n/a

Maintain=0 Release=1

Generator Voltage Pre-position 1

42222

Float

4

R W

Volt

Setpoint adjustment range determined
by registers 42228 and 42230.

Generator Voltage Pre-position Mode 2

42224

Uint32

4

R W

n/a

Maintain=0 Release=1

Generator Voltage Pre-position 2

42226

Float

4

R W

Volt

Setpoint adjustment range determined
by registers 42228 and 42230.

Generator Voltage Minimum Setpoint
Limit

42228

Float

4

R W

Percent

70 - 120

Generator Voltage Maximum Setpoint
Limit

42230

Float

4

R W

Percent

70 - 120

Generator var Setpoint

42232

Float

4

R W

kilovar

Setpoint adjustment range determined
by registers 42244 and 42246.

Generator var Traverse Rate

42234

Float

4

R W

Second

10 - 200

Generator var Pre-position Mode 1

42236

Uint32

4

R W

n/a

Maintain=0 Release=1

Generator var Pre-position 1

42238

Float

4

R W

kilovar

Setpoint adjustment range determined
by registers 42244 and 42246.

Generator var Pre-position Mode 2

42240

Uint32

4

R W

n/a

Maintain=0 Release=1

Generator var Pre-position 2

42242

Float

4

R W

kilovar

Setpoint adjustment range determined
by registers 42244 and 42246.

Generator var Minimum Setpoint Limit

42244

Float

4

R W

Percent

-100 – 100

Generator var Maximum Setpoint Limit

42246

Float

4

R W

Percent

-100 – 100

Generator PF Setpoint

42248

Float

4

R W

Power Factor

Setpoint adjustment range determined
by registers 42260 and 42262.

Generator PF Traverse Rate

42250

Float

4

R W

Second

10 – 200

Generator PF Pre-position Mode 1

42252

Uint32

4

R W

n/a

Maintain=0 Release=1

Generator PF Pre-position 1

42254

Float

4

R W

Power Factor

Setpoint adjustment range determined
by registers 42260 and 42262.

Generator PF Pre-position Mode 2

42256

Uint32

4

R W

n/a

Maintain=0 Release=1

Generator PF Pre-position 2

42258

Float

4

R W

Power Factor

Setpoint adjustment range determined
by registers 42260 and 42262.

Generator PF Minimum Setpoint Limit

42260

Float

4

R W

Power Factor

0.5 – 1

Generator PF Maximum Setpoint Limit

42262

Float

4

R W

Power Factor

-1 – -0.5

FVR Setpoint

42264

Float

4

R W

Volt

Setpoint adjustment range determined
by registers 42276 and 42278.

FVR Traverse Rate

42266

Float

4

R W

Second

10 – 200

FVR Pre-position Mode 1

42268

Uint32

4

R W

n/a

Maintain=0 Release=1

FVR Pre-position 1

42270

Float

4

R W

Volt

Setpoint adjustment range determined
by registers 42276 and 42278.

FVR Pre-position Mode 2

42272

Uint32

4

R W

n/a

Maintain=0 Release=1

FVR Pre-position 2

42274

Float

4

R W

Volt

Setpoint adjustment range determined
by registers 42276 and 42278.

FVR Minimum Setpoint Limit

42276

Float

4

R W

Percent

0 - 150

FVR Maximum Setpoint Limit

42278

Float

4

R W

Percent

0 - 150