beautypg.com

Power connections, Power connections -7 – Carrier Access Network Device Axxius 800 User Manual

Page 63

background image

Axxius 800 - Release 2.2

3-7

Electrical Installation and Cabling

Chassis Connections

Power Connections

There are three power supplies available with the Axxius 800; 24 VDC and 48 VDC
and 48 VDC NI, all use this connector. The Axxius 800 supports a redundant power
system, therefore there is INPUT (power) P1 and P2.

Input Power

A separate

fuse should be used for each DC input

NOTE:

If two power supplies are installed into the system they MUST be

of the same type (24 VDC, 48 VDC or 48 VDC NI).

Wire each connector to a power source:

1. Ensure that no power is present on the two wires to be connected.

DANGER!

P

OSSIBLE

SHOCK

HAZARD

EXISTS

,

PLEASE

FOLLOW

INSTRUCTIONS

CAREFULLY

.

2. Strip the two wires from the power source so that approximately 5/16 inch of

bare wire is exposed. 16

or

18

AWG

insulated

copper

wire

is recommended

for power

connections.

3. Insert the Battery Return and DC wires into the appropriate square holes, one

at a time.

4. Tighten screws to clamp wires.

Power Supply

Rated Amperage

Recommended External
Input Fuse

24 VDC

5 Amp

7 Amp

48 VDC/48 VDC NI

2.5 Amp

3.5 Amp