Alarms, Test alarm, Identify alarm – Carrier Access Network Device Axxius 800 User Manual
Page 512
C-2
Axxius 800 - Release 2.2
Loopback Tests
Alarms
Alarms
Test Alarm
The Axxius 800 alarm functions can be manually tested using the following command
for setting critical, major and minor alarms. Turning alarms on or off will produce
alarm messages and log entries stating the alarm event was manually set/cleared by the
user.
Syntax:
set alarms {critical|major|minor} {off|on}
Identify Alarm
Alarm indicators
l
LEDs - When an Alarm is triggered, the LED will display a red/yellow
indicator light, which will stay on until the Alarm is cleared. The following
is the LED information for the Control Panel Interface card. For LED
information for a specific service card see the chapter for that card
.
LED
State
Description
CRITICAL
Off
No critical alarms present
Red
Critical alarms present
MAJOR
Off
No major alarms present
Red
Major alarm present
MINOR
Off
No minor alarms present
Red
Minor alarms present
ACO
Off
Normal mode. No alarms are being
suppressed.
Red
Alarm cutoff active. One or more active
alarms suppressed.