L

EDS94ARNExxxx EN 2.3 - 06/2014

5.6

"State bus" monitoring function

The state bus has been designed exclusively for Lenze controllers. The bus system can

interconnect up to 20 controllers and can be used to simulate the function of a "rip cord":

[5-1]

Schematic diagram: Networking via state bus

The state bus only knows the states "OK" and "Error".

The state bus is a multi-master bus system, i.e. each node connected to the state bus

can set the state bus to the "Error" state by setting it to LOW level.

In the "Error" state, all nodes initiate their adjustable response, e.g. synchronised

braking of the drive system to standstill.

The "Error" state is also set if a node connected to the state bus is not supplied with

voltage.

X2/SB = State bus In/Out (reference potential GE)

X2

X2

X2

GE

24E

SB

GE

24E

SB

GE

24E

SB

Note!

Exception handling:
• In the case of a critical exception within the application (e.g. reset), the "rip

cord" is not "pulled", the state bus remains in the "OK" state.