Brake resistor: i·xt overload [0x007b001d, Brake transistor: overcurrent [0x007b0021, Failure of mains phase l1 [0x007b002d – Lenze E94ARNE Regenerative power supply User Manual
Page 227: Failure of mains phase l2 [0x007b002e, Failure of mains phase l3 [0x007b002f, 0x007b001d, 0x007b0021, 0x007b002d, 0x007b002e, 0x007b002f
EDS94ARNExxxx EN 2.3 - 06/2014
L
227
9400 regenerative power supply module | Parameter setting
Diagnostics & fault analysis
Error messages
Brake resistor: I²xt overload [0x007b001d]
Brake transistor: Overcurrent [0x007b0021]
Failure of mains phase L1 [0x007b002d]
Failure of mains phase L2 [0x007b002e]
Failure of mains phase L3 [0x007b002f]
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
Too frequent and too long brake operations.
• Check drive dimensioning.
• Check parameter setting (
).
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
Brake chopper short circuit/earth fault detected.
Check brake chopper cable and brake resistor.
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
Interruption of phase L1 of the mains cable.
•
Up to software version V02.00.19
a fault is reported if
a mains phase failure occurs.
•
From software version V02.00.20
a trouble is reported
for mains phase failures < 500 ms. If the mains phase
failure is pending longer than 500 ms, the device
changes to the "Fault" status.
If the fault is pending longer and the device reports a
fault, check the cabling between the regenerative power
supply module and the mains.
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
Interruption of phase L2 of the mains cable.
•
Up to software version V02.00.19
a fault is reported if
a mains phase failure occurs.
•
From software version V02.00.20
a trouble is reported
for mains phase failures < 500 ms. If the mains phase
failure is pending longer than 500 ms, the device
changes to the "Fault" status.
If the fault is pending longer and the device reports a
fault, check the cabling between the regenerative power
supply module and the mains.
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
Interruption of phase L3 of the mains cable.
•
Up to software version V02.00.19
a fault is reported if
a mains phase failure occurs.
•
From software version V02.00.20
a trouble is reported
for mains phase failures < 500 ms. If the mains phase
failure is pending longer than 500 ms, the device
changes to the "Fault" status.
If the fault is pending longer and the device reports a
fault, check the cabling between the regenerative power
supply module and the mains.