beautypg.com

I-1010 – Lenze E94ARNE Regenerative power supply User Manual

Page 151

background image

EDS94ARNExxxx EN 2.3 - 06/2014

L

151

9400 regenerative power supply module | Parameter setting

"CAN on board" system bus

Implemented CANopen objects

I-1010

Saving the parameters with mains failure protection.

Corresponds to the device command

C00002

= "11: Save start parameters".

This command serves to store the current parameter settings of the active application

with mains failure protection in the memory module of the regenerative power supply

module.

Reading subindex 1

[6-3]

Assignment of the data telegram (read access)

Writing to subindex 1
In addition to index and subindex, the telegram data must include the signature “save“

(ASCII characters; ISO 8859) to start the parameter saving (see table).

A response according to the specification DS301 V4.02 occurs when a wrong identifier

is used for writing.

[6-4]

Assignment of the data telegram (write access)

Index:

I-1010

Name:

Store parameters

Subindex

Default setting

Setting range (min. value | unit | max. value)

Access

Data type

0: Highest subindex supported

1

- (read access only)

ro

U32

1: Save all parameters

-

0

4294967295 rw

U32

Subindex

Meaning
Reading

Writing

0

Max. number of supported subindexes: 1 -

(A write attempt results in the error

message 0x06010002.)

1

Reading of the storing functionality of all

parameters.

Saving the parameters with mains

failure protection.

8th byte

7th byte

6th byte

5th byte

Data 4

Data 3

Data 2

Data 1

Bit 31 ... bit 2

Bit 1

Bit 0

0

0/1

0/1

Bit

Meaning

Bit 0

0 Saving of parameters on command not possible.
1 Saving of parameters on command possible (Lenze).

Bit 1

0 Automatic saving of parameters not possible (Lenze).
1 Automatic saving of parameters possible.

8th byte

7th byte

6th byte

5th byte

Data 4

Data 3

Data 2

Data 1

"e" = 0x65

"v" = 0x76

"a" = 0x61

"s" = 0x73