Error in control configuration [0x006a0017, 0x006f0000, 0x006a0017 – Lenze E94ARNE Regenerative power supply User Manual
Page 220: 0x006a0015, 0x006a0016, Diagnostics & fault analysis error messages

9400 regenerative power supply module | Parameter setting
Diagnostics & fault analysis
Error messages
220
L
EDS94ARNExxxx EN 2.3 - 06/2014
PDO mapping (MXI1): Faulty configuration [0x006a0015]
PDO mapping (MXI2): Faulty configuration [0x006a0016]
Error in control configuration [0x006a0017]
Control card: Supply voltage (24 V DC) too low [0x006f0000]
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
CANopen communication module in MXI1: Incorrectly
configured process data mapping.
• The corresponding PDO channel is not installed, since,
for instance, no communication module has been
selected for the module slot MXI1 in the Engineer
project.
• The communication module selected for the module
slot MXI1 in the Engineer project does not support
PDO mapping.
• The mapping information transferred to the
regenerative power supply module is incorrect.
• Integrate suitable communication module into the
Engineer project for the module slot MXI1.
• Check the configuration of the network. Then
recompile the project and transfer it to the
regenerative power supply module.
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
CANopen communication module in MXI2: Incorrectly
configured process data mapping.
• The corresponding PDO channel is not installed, since,
for instance, no communication module has been
selected for the module slot MXI2 in the Engineer
project.
• The communication module selected for the module
slot MXI2 in the Engineer project does not support
PDO mapping.
• The mapping information transferred to the
regenerative power supply module is incorrect.
• Integrate suitable communication module into the
Engineer project for the module slot MXI2.
• Check the configuration of the network. Then
recompile the project and transfer it to the
regenerative power supply module.
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
An invalid control configuration has occurred.
Load another application.
Response (Lenze setting printed in bold)
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
External 24V voltage supply of the control card is lower
than 18 V.
Check external supply voltage.
• If the external supply voltage is available and the
error message still occurs, contact Lenze.