beautypg.com

Can on board: lifeguarding error [0x00840020, 0x00850000, 0x00840021 – Lenze E94ARNE Regenerative power supply User Manual

Page 233: 0x00840000, 0x00840020, Diagnostics & fault analysis error messages

background image

EDS94ARNExxxx EN 2.3 - 06/2014

L

233

9400 regenerative power supply module | Parameter setting

Diagnostics & fault analysis

Error messages

CAN on board: Heartbeat error index 1 ... 32 [0x00840000 ... 0x0084001f]

CAN on board: Lifeguarding error [0x00840020]

CAN on board: Faulty NMT slave configuration [0x00840021]

CAN on board: Faulty emergency configuration [0x00850000]

Response (Lenze setting printed in bold)

Setting:

C00613/1...32

( adjustable response)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

CAN on board: Cyclic node monitoring

• Node has not received a heartbeat telegram from

node 1 ... 32 within the defined time.

• Reactivate CAN node by mains switching, restart of

the regenerative power supply module,

(

C00002

="11000") or CAN reset node.

• Reparameterise the heartbeat producer monitoring

time or switch off monitoring and reset locked error

status, if necessary.

Tip: Save the current parameter set before mains

switching and restarting the regenerative power supply

module (

C00

002

="11").

Response (Lenze setting printed in bold)

Setting:

C00614

( Adjustable response)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

CAN on board: Cyclic node monitoring

• Slave response: Maximum time between two node

guarding telegrams (remote transmission request

telegram) from the master has been exceeded.

Reparameterise the life guarding monitoring time or

switch off monitoring.

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

CAN on board: A configuration error has occurred in the

network management of the CAN slave.

• Faulty download of an Engineer or PLC Designer

project

• Invalid CAN settings according to DS301V402 in the

Engineer or PLC Designer.

• Incorrect parameterisation of node guarding or

heartbeat.

• Repeat download

• Correct CAN settings in the project and regenerate

project.

Response (Lenze setting printed in bold)

None  System fault  Fault  Trouble  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

CAN on board: CAN emergency configuration is faulty

• Faulty download of an Engineer or PLC Designer

project

• Invalid CAN emergency settings according to

DS301V402 in the Engineer or PLC Designer.

• Repeat download

• Correct CAN settings in the project and regenerate

project.